7-6
W650 Wind Generator Protection System
GEK-113032A
7.2 IEC 61850 PROFILE FOR W650
7 IEC 61850 PROTOCOL
7
7.2IEC 61850 PROFILE FOR W650
7.2.1 INTRODUCTION
IEC61850 is a series of standards describing client/server and peer-to-peer communications, substation design and
configuration, testing environmental and project standards.
The W650 relay supports IEC61850 server services over TCP/IP. This profile requires the W650 to have an IP address to
establish communications. It is possible to have up to five simultaneous connections.
A built-in TCP/IP connection timeout of two minutes is employed by the W650 to detect “dead” connections. If there is no
data traffic on a TCP connection for greater than two minutes, the connection will be aborted by the server. Therefore, when
using IEC61850 reporting, clients should configure report control block items such that an integrity report will be issued al
least every 2 minutes. If other MMS data is being polled on the same connection al least once every 2 minutes, this timeout
will not apply.
The exact structure and values of the supported IEC61850 logical nodes can be seen by connecting to a W650 relay with
an MMS browser, such as “MMS Object Explorer and AXS4-MMS” DDE/OPC server from Sisco Inc.
Peer-to-peer communication of a digital state information ( remote inputs/outputs ) is supported using the IEC61850 GSSE
services. This feature allows digital points to be exchanged between IEC 61850 conforming devices.
MMS file services are supported to allow transfer of oscillography, event record, or other files from a W650 relay.
7.2.2 ACSI CONFORMANCE STATEMENT
7.2.2.1 ACSI BASIC CONFORMANCE STATEMENT
SERVER/
PUBLISHER
W650
CLIENT-SERVER ROLES
B11
Server
side (of TWO-PARTY APPLICATION-ASSOCIATION)
C1
Yes
B12
Client
side (of TWO-PARTY APPLICATION-ASSOCIATION)
---
SCSMS SUPPORTED
B21
SCSM:
IEC 61850-8-1 used
Yes
B22
SCSM:
IEC 61850-9-1 used
B23
SCSM:
IEC 61850-9-2 used
B24
SCSM:
other
GENERIC SUBSTATION EVENT MODEL (GSE)
B31
Publisher
side O
Yes
B32
Suscriber
side ---
Yes
TRANSMISSION OF SAMPLED VALUE MODEL (SVC)
B41
Publisher
side O
B42
Suscriber
side ---
c1- shall be 'M' if support for
LOGICAL-DEVICE
model has been declared.
O - Optional
M - Mandatory
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...