1-16
W650 Wind Generator Protection System
GEK-113032A
1.3 ENERVISTA 650 SETUP SOFTWARE
1 GETTING STARTED
1
1.3.3 CONNECTING ENERVISTA 650 SETUP WITHW650
This section is intended as a quick start guide to using the EnerVista 650 Setup software. Please refer to section 4.1 in this
manual for more information about the EnerVista 650 Setup software interface.
a) CONFIGURING AN ETHERNET CONNECTION
Before starting, verify that the Ethernet network cable is properly connected to the Ethernet port on the back of the relay.
1. Install and start the latest version of the EnerVista 650 Setup software (available from the GE EnerVista CD or online
from
http://www.GEindustrial.com/multilin
(see previous section for installation instructions).
2. Go to “
Communication>Computer
” and enter the following data refering to communications:
3. Select Control Type as MODBUS TCP/IP from the drop-down list. This option will display a number of interface
parameters that must be entered for proper Ethernet communications.
4. Enter the relay IP address (from “
Setpoint>Product Setup >Communication Settings>Network>IP ADDRESS
”) in
the IP Address field in MODBUS TCP/IP SETUP.
5. Enter the relay ModBus address (from “
Setpoint>Product Setup >Communication Settings>ModBus
Protocol>ModBus Address COM1/COM2 setting
”) in the Unit Identifier (Slave Address) field.
6. Enter the ModBus port address (from “
Setpoint>Product Setup >Communication Settings>ModBus
Protocol>ModBus Port Number
” setting) in the ModBus Port field.
7.The Device has now been configured for Ethernet communications. Proceed to press the ON button to begin
communicating.
b) CONFIGURING AN RS232 CONNECTION
Before starting, verify that the RS232 serial cable is properly connected to the RS232 port on the front panel of the relay.
1. Install and start the latest version of the EnerVista 650 Setup software (available from the GE EnerVista CD or online
from
http://www.GEindustrial.com/multilin
(see previous section for installation instructions).
2. Go to “
Communication>Computer
” and enter the following data referred to communications:
3. Select Control Type as No Control Type from the drop-down list. This option will display a number of interface
parameters that must be entered for proper serial communications.
4. Enter the relay Slave Address (“
Setpoint>Product Setup >Communication Settings>ModBus Protocol
” menu) in the
Slave Address field.
5. Enter the physical communications parameters (Baudrate and parity settings) from
“Setpoint>Product Setup
>Communication Settings>Serial Ports
” menu, in their respective fields.
6.The Device has now been configured for RS232 communications. Proceed to press the ON button to begin
communicating.
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...