GEK-113032A
W650 Wind Generator Protection System
5-91
5 SETTINGS
5.6 INPUTS/OUTPUTS
5
5.6.3 INPUTS
5.6.3.1 INPUT SETTINGS DESCRIPTION
Input Activation Voltage Threshold:
The range of this value goes from 20 to 230 volts. There is a single setting for all
inputs in the same group (inputs sharing the same common). In mixed and supervision boards there are two groups of
inputs, called A and B., in 32DI board there are four groups of 8 inputs each.
Debounce Time:
This is the debounce time set for inputs (1 to 50 ms). The debounce time is the time window for input
filtering. If an input suffers a change of level that lasts less than this set time, the change will not be considered. There is a
single setting for all inputs in the same group.
Input Type:
Type of logic associated to the physical input. Possible settings are, positive and negative.
Positive and Negative settings correspond to signals that re activated or deactivated with the input level, considering the
delay setting. Positive-edge, and Negative-edge settings correspond to signals that are activated with the change of the
input signal; in this case, the Delay Input Time will not be considered, only the Debounce Time; this edge signals are
deactivated automatically after one PLC scan cycle. shows the types of signals associated to the different input
configuration types.
Delay Input Time:
This is the delay applied to the input signal; the default value is zero, meaning no delay; the setting
range is 0 to 60000 milliseconds (1 minute). This setting is used in slow switchgear applications.
This is not a grouped setting; there is a different setting for each input. It is important to distinguish between this
delay
input time
and the
debounce time
used for filtering undesired transients in the input signal. The Debounce time is always
added to the delay input time.
Figure 5–23: INPUT LOGIC TYPES
Содержание Multilin W650
Страница 2: ......
Страница 10: ...VIII W650 Wind Generator Protection System GEK 113032A TABLE OF CONTENTS ...
Страница 30: ...1 20 W650 Wind Generator Protection System GEK 113032A 1 4 W650 HARDWARE 1 GETTING STARTED 1 ...
Страница 140: ...4 72 W650 Wind Generator Protection System GEK 113032A 4 3 WEB SERVER 4 HUMAN INTERFACES 4 ...
Страница 360: ...7 48 W650 Wind Generator Protection System GEK 113032A 7 2 IEC 61850 PROFILE FOR W650 7 IEC 61850 PROTOCOL 7 ...
Страница 368: ...8 8 W650 Wind Generator Protection System GEK 113032A 8 4 OBJECT DICTIONARY 8 W650 CANOPEN PROFILE 8 ...
Страница 406: ...11 22 W650 Wind Generator Protection System GEK 113032A 11 15 RECLOSER 79 11 COMMISSIONING 11 ...
Страница 422: ...13 6 W650 Wind Generator Protection System GEK 113032A 13 4 RELAY CONFIGURATION 13 FREQUENTLY ASKED QUESTIONS 13 ...
Страница 446: ...A 22 W650 Wind Generator Protection System GEK 113032A A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 596: ...D 8 W650 Wind Generator Protection System GEK 113032A D 5 IEC 60870 5 104 POINT LIST APPENDIXD D ...
Страница 622: ...F 2 W650 Wind Generator Protection System GEK 113032A F 1 GE MULTILIN WARRANTY APPENDIXF F ...