CHAPTER 4: PROGRAMMING
S1 PQM SETUP
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–7
4.2.4
RS485/RS232
Serial Ports
FIGURE 4–4: Setpoints Page 1 – PQM Setup / Communication Ports
•
MODBUS COMMUNICATION ADDRESS:
Enter a unique address from
1
to
255
for the
PQM. The selected address is used for all three serial communication ports. A message
sent with address 0 is a broadcast message to which all PQMs will listen but not
respond. Although addresses do not have to be sequential, no two PQMs can have the
same address or there will be conflicts resulting in errors. Generally, each PQM added
to the link will use the next higher address, starting from address 1.
•
BAUD RATE:
Enter the baud rate for each port:
1200
,
2400
,
4800
,
9600
, or
19200
baud. All
PQMs and the computer on the RS485 communication link must run at the same baud
rate. The fastest response is obtained at 19200 baud. Use slower baud rates if noise
becomes a problem. The data frame consists of 1 start bit, 8 data bits, 1 stop bit and a
programmable parity bit. The
BAUD RATE
default setting is 9600.
•
PARITY:
Enter the parity for each communication port: EVEN, ODD, or NONE. All PQMs
on the RS485 communication link and the computer connecting them must have the
same parity.
]] SETPOINTS
]] S1 PQM SETUP
] COM1 RS485
] SERIAL PORT
MODBUS COMMUNICATION
ADDRESS:
1
COM1 BAUD RATE:
9600 BAUD
COM1 PARITY: NONE
]] SETPOINTS
]] S2 SYSTEM SETUP
SETPOINT
Range: 1 to 255; Step 1
Range: 1200, 2400, 4800,
9600, 19200
R a n g e : N O N E , E V E N ,
ODD
] PREFERENCES
]
] SETPOINT ACCESS
]
] COM2 RS485
] SERIAL PORT
COM2 BAUD RATE:
9600 BAUD
COM2 PARITY: NONE
] FRONT PANEL RS232
] SERIAL PORT
RS232 BAUD RATE:
9600 BAUD
RS232 PARITY: NONE
M E S S A G E
M E S S A G E
M E S S A G E
M E S S A G E
Range: 1200, 2400, 4800,
9600, 19200
Range: 1200, 2400, 4800,
9600, 19200
R a n g e : N O N E , E V E N ,
ODD
R a n g e : N O N E , E V E N ,
ODD
M E S S A G E
M E S S A G E
M E S S A G E
Содержание Multilin PQM