CHAPTER 8: DNP COMMUNICATIONS
DNP 3.0 PROTOCOL
PQM POWER QUALITY METER – INSTRUCTION MANUAL
8–9
8.1.6
Binary Output
/ Control Relay
Output Point
List
77
Alarm active: Negative reactive demand
Class 1
78
Alarm active: Pulse input 2
Class 1
79
Alarm active: Pulse input 3
Class 1
80
Alarm active: Pulse input 4
Class 1
81
Alarm active: Pulse input total
Class 1
82
Alarm active: Time
Class 1
*Binary Input Change does not apply.
This point is also reflected in the corresponding internal indication (IIN) bit in each
response header.
Table 8–2: Point List for Binary Input (Object 01) / Binary Input Change (Object
INDEX
DESCRIPTION
EVENT CLASS
ASSIGNED TO
NOTES
Table 8–3: Point List for Binary Output (Object 10)
Control Relay Output Block (Object 12)
INDEX
DESCRIPTION
0
*
Reset
1
Alarm relay on
2
Alarm relay off
3
Auxiliary relay 1 on
4
Auxiliary relay 1 off
5
Auxiliary relay 2 on
6
Auxiliary relay 2 off
7
Auxiliary relay 3 on
8
Auxiliary relay 3 off
Display 40 character flash message for 5 seconds (Display
message must be set up using Modbus)
Clear energy values
Clear max. demand values
Clear min./max current values
Clear min./max voltage values
Clear min./max power values
Clear max. THD values
16*
Clear switch input pulse count
Clear event record
Simulate “SETPOINT” keypress
19*
Simulate “ACTUAL” keypress
Содержание Multilin PQM