CHAPTER 4: PROGRAMMING
S4 ALARMS/CONTROL
PQM POWER QUALITY METER – INSTRUCTION MANUAL
4–47
•
OVERFREQUENCY DELAY
: If the overfrequency equals or exceeds the
OVERFREQUENCY LEVEL
setpoint value for the time delay programmed in this
setpoint, an overfrequency condition will occur.
4.5.4
Power Alarms
FIGURE 4–27: Setpoints Page 4 – Alarms/Control / Power
•
POWER ALARMS LEVEL BASE UNITS:
This setpoint is used to select the base unit
multiplier for all power alarms. When set to
kW/kVAR
, all power alarm levels can be set
in terms of kW and kVAR with a step value of 1 kW/kVAR. When set to
MW/MVAR
, all
power alarm levels can be set in terms of MW and MVAR with a step value of 0.01 MW/
MVAR.
•
POSITIVE REAL POWER RELAY:
Positive real power level detection can either be
disabled, used as an alarm or as a process control. Set this setpoint to off if the feature
is not required. Selecting alarm relay will cause the alarm relay to activate and display
an alarm message whenever a positive real power level exceeds the selected level.
]] SETPOINTS
]] S4 ALARMS/CONTROL
] POWER
]
POWER ALARMS LEVEL
BASE UNITS: kW/kVAR
POSITIVE REAL POWER
RELAY: OFF
POSITIVE REAL POWER
LEVEL
t
1000 kW
]] SETPOINTS
]] S5 TESTING
SETPOINT
Range: kW/kVAR, MW/MVAR
Range: ALARM, AUX1, AUX2, AUX3, OFF
POSITIVE REAL POWER
DELAY: 10.0 s
NEGATIVE REAL POWER
RELAY: OFF
NEGATIVE REAL POWER
LEVEL
t
1000 kW
] CURRENT/VOLTAGE
]
Range: 0.5 to 600.0; Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 0.5 to 600.0; Step 0.5 s
NEGATIVE REAL POWER
DELAY: 10.0 s
POSITIVE REACT POWER
RELAY: OFF
POSITIVE REACT POWER
LEVEL
t
1000 kvar
POSITIVE REACT POWER
DELAY: 10.0 s
NEGATIVE REACT POWER
RELAY: OFF
NEGATIVE REACT POWER
LEVEL
t
1000 kvar
NEGATIVE REACT POWER
DELAY: 10.0 s
Range: 1 to 65000, Step 1 kW
0.01 to 650.00, Step 0.01 MW **
Range: ALARM, AUX1, AUX2,
AUX3, OFF
Range: 0.5 to 600.0
Step 0.5 s
Range: 0.5 to 600.0
Step 0.5 s
Range: ALARM, AUX1, AUX2,
AUX3, OFF
MESSAGE
MESSAGE
Range: 1 to 65000, Step 1 kW
0.01 to 650.00, Step 0.01 MW **
Range: 1 to 65000, Step 1 kvar
0.01 to 650.00, Step 0.01 Mvar **
Range: 1 to 65000, Step 1 kvar
0.01 to 650.00, Step 0.01 Mvar **
**
These setpoint ranges are dependent upon the
POWER ALARMS LEVEL BASE UNITS
setpoint.
If
POWER ALARMS LEVEL BASE UNITS
=
kW/kVAR
, then the ranges are in kW/kvar.
If
POWER ALARM LEVEL BASE UNITS
=
MW/Mvar
, then the ranges are in MW/Mvar
MESSAGE