3-66
G650 Generator Protection & Control System
GEK-113328A
3.3 WEB SERVER
3 HUMAN INTERFACES. SETTINGS & ACTUAL VALUES
3
3.3.6 FAULT REPORT
The fault report screen provides access to the last 10 fault reports obtained by the relay. These records are stored
according to an index that marks their position among all records produced in the relay, with a range from 1 to 999,
returning to 1 in case of exceeding the limit of 999. As in the case of oscillography records, the highest index corresponds
to the most recent record.
In the fault report, oscillography and data logger screens, the system will request acceptance of a safety-warning message.
Figure 3–39: FAULT REPORT SCREEN
The information provided in this screen includes the date and time when the fault was registered, fault calculations such as
distance to the fault, type of fault, date and time, and the line parameters, as well as the recloser and breaker status during
the fault.
This screen shows also prefault and fault voltage and current primary values. At the top of the screen, associated to the
trigger event number there is a button labeled as
INFO
. This button displays at the bottom of the screen the events
produced before and after the fault report trigger, so that the user has very useful information about the moment when the
fault was produced.
To obtain a text file with all the fault report information, press the
Download
option and save the file in the computer.
Содержание Multilin GEK-113328A
Страница 2: ......
Страница 6: ...4 G650 Generator Protection Control System GEK 113328 TABLE OF CONTENTS ...
Страница 26: ...1 20 G650 Generator Protection Control System GEK 113328A 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 170: ...7 6 G650 Generator Protection Control System GEK 113328A 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 185: ...GEK 113328A G650 Generator Protection Control System A 11 APPENDIX A A 1 FACTORY DEFAULT LOGIC A ...
Страница 186: ...A 12 G650 Generator Protection Control System GEK 113328A A 1 FACTORY DEFAULT LOGIC APPENDIXA A ...
Страница 218: ...C 2 G650 Generator Protection Control System GEK 113328A C 1 GE MULTILIN WARRANTY APPENDIXC C ...