GEK-113000T
F650 Digital Bay Controller
6-23
6 COMMISSIONING
6.16 RECLOSER (79)
6
6.16 RECLOSER (79)
Set protection element 79 as follows:
Set the relay to trip by 50PH, and configure the signals necessary to test the 79 element:
Configure one output as AR RECLOSE
Configure the AR INITIATE signal with the 50PH trip
Configure the AR LEVEL BLOCK signal with a digital input
Configure the AR CONDS INPUT with the digital signal desired
6.16.1 RECLOSING CYCLE
Connect a latching relay simulating the breaker managed by the F650 unit.
Once the relay is set, close the breaker and wait for 5 seconds.
After this time, the recloser is ready to initiate the reclosing cycle.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 2.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 4.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 6.1 seconds.
Command a 50PH trip and verify that the breaker opens and the relay recloses in 8.1 seconds.
Command a 50PH trip and verify that the breaker opens and the recloser passes to Lockout.
Verify the correct operation of programmed outputs
Tripping times must be within the following values:
RECLOSER
Function
ENABLED
Max Number Shots
4
Dead Time 1
2.10 sec
Dead Time 2
4.10 sec
Dead Time 3
6.10 sec
Dead Time 4
8.10 sec
Reclaim Time
3.00 sec
Cond. Permission
ENABLED
Hold Time
7.00 sec
Reset Time
5.00 sec
50PH SETTINGS
Function
ENABLED
Input
RMS
Pickup Level
3 A
Trip Delay
0.00 s
Reset Delay
0.00 s
RECLOSING CYCLE
Nº shot
Expected time
Admissible time
1
2.1 sec
[1.8 – 2.3]
2
4.1 sec
[3.8 – 4.3]
3
6.1 sec
[5.8 – 6.3]
4
8.1 sec
[7.8 – 8.3]
Содержание Multilin GEK-113000T
Страница 5: ...4 F650 Digital Bay Controller GEK 113000T TABLE OF CONTENTS ...
Страница 25: ...1 20 F650 Digital Bay Controller GEK 113000T 1 4 650 HARDWARE 1 GETTING STARTED 1 ...
Страница 127: ...3 70 F650 Digital Bay Controller GEK 113000T 3 3 WEB SERVER 3 HUMAN INTERFACES SETTINGS ACTUAL VALUES 3 ...
Страница 169: ...6 26 F650 Digital Bay Controller GEK 113000T 6 17 THERMAL IMAGE ELEMENT 49 6 COMMISSIONING 6 ...
Страница 175: ...7 6 F650 Digital Bay Controller GEK 113000T 7 4 RELAY CONFIGURATION 7 FREQUENTLY ASKED QUESTIONS 7 ...
Страница 215: ...A 36 F650 Digital Bay Controller GEK 113000T A 1 LOGIC OPERANDS APPENDIXA A ...
Страница 259: ...D 2 F650 Digital Bay Controller GEK 113000T D 1 GE MULTILIN WARRANTY APPENDIXD D ...