APPENDIX B
B.4 MEMORY MAPPING
B
E246
PMU Aggregator 1 PDC Network Control
0 to 1
---
1
F102
0 (Disabled)
E247
Aggregator 1 Include PMU1
0 to 1
---
1
F126
0 (No)
E248
Aggregator 1 Include PMU2
0 to 1
---
1
F126
0 (No)
E249
Aggregator 1 Include PMU3
0 to 1
---
1
F126
0 (No)
E24A
Aggregator 1 Include PMU4
0 to 1
---
1
F126
0 (No)
E24B
PMU Aggregator 1 ASDUS
1 to 4
---
1
F001
1
E24C
PMU Aggregator 1 Port
1 to 3
---
1
F001
1
E24D
PMU Aggregator 1 Reserved (3 items)
0 to 1
---
1
F001
0
Phasor Measurement Unit Recording Command (Read/Write Command)
E4D4
PMU 1 Recording Clear Command
0 to 1
---
1
F126
0 (No)
E4D5
PMU 1 Recording Force Trigger
0 to 1
---
1
F126
0 (No)
Phasor Measurement Unit Recording (Read/Write Setting)
E4DC
PMU 1 Record Function
0 to 1
---
1
F102
0 (Disabled)
E4DD
PMU 1 No of Timed Records
2 to 128
---
1
F001
10
E4DE
PMU 1 Trigger Mode
0 to 1
---
1
F542
0 (Auto
Overwrite)
E4DF
PMU 1 Timed Trigger Position
1 to 50
%
1
F001
10
Phasor Measurement Unit Aggregator Control Block (Read/Write Setting)
E650
PMU Aggregator 1 Control Block SvEna
0 to 4294967295
---
1
F300
0
E652
PMU Aggregator 1 Control Block Client Control
0 to 4294967295
---
1
F300
0
E654
PMU Aggregator 1 CB SvEna Default
0 to 4294967295
---
1
F300
0
E656
PMU Aggregator 1 Control Block ConfRev
1 to 4294967295
---
1
F003
1
E658
PMU Aggregator 1 Control Block Priority
0 to 7
---
1
F001
4
E659
PMU Aggregator 1 Control Block IPClass
0 to 1
---
1
F563
1 (Expedited
Forwarding)
E65A
PMU Aggregator 1 Control Block VID
0 to 4095
---
1
F001
0
E65B
PMU Aggregator 1 Control Block APPID
0 to 16383
---
1
F001
0
E65C
PMU Aggregator 1 Control Block IP Address
0 to 4294967295
---
1
F003
0
E65E
PMU Aggregator 1 Control Block Security
0 to 2
---
1
F001
0
DNP/IEC Points (Read/Write Setting)
E700
DNP/IEC 60870-5-104 Binary Input Points (256 items)
0 to 4294967295
---
1
F300
0
E900
DNP/IEC 60870-5-104 Analog Input Points (256 items)
0 to 65535
---
1
F300
0
Synchrocheck (Read/Write Setting) (4 modules)
EC00
Synchrocheck 1 Function
0 to 1
---
1
F102
0 (Disabled)
EC01
Synchrocheck 1 V1 Source
0 to 5
---
1
F167
0 (SRC 1)
EC02
Synchrocheck 1 V2 Source
0 to 5
---
1
F167
1 (SRC 2)
EC03
Synchrocheck 1 Maximum Voltage Difference
0 to 400000
V
1
F060
10000
EC05
Synchrocheck 1 Maximum Angle Difference
0 to 100
degrees
1
F001
30
EC06
Synchrocheck 1 Maximum Frequency Difference
0 to 2
Hz
0.01
F001
100
EC07
Synchrocheck 1 Dead Source Select
0 to 5
---
1
F176
1 (LV1 and DV2)
EC08
Synchrocheck 1 Dead V1 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
EC09
Synchrocheck 1 Dead V2 Maximum Voltage
0 to 1.25
pu
0.01
F001
30
EC0A
Synchrocheck 1 Live V1 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
EC0B
Synchrocheck 1 Live V2 Minimum Voltage
0 to 1.25
pu
0.01
F001
70
EC0C
Synchrocheck 1 Target
0 to 2
---
1
F109
0 (Self-reset)
EC0D
Synchrocheck 1 Events
0 to 1
---
1
F102
0 (Disabled)
EC0E
Synchrocheck 1 Block
0 to 4294967295
---
1
F300
0
EC10
Synchrocheck 1 Frequency Hysteresis
0 to 0.1
Hz
0.01
F001
6
EC11
...Repeated for Synchrocheck 2
EC22
...Repeated for Synchrocheck 3
EC33
...Repeated for Synchrocheck 4
Phasor Measurement Unit Frequency Trigger (Read/Write Setting)
ECCC
PMU 1 Frequency Trigger Function
0 to 1
---
1
F102
0 (Disabled)
ECCD
PMU 1 Frequency Trigger Low Frequency
20 to 70
Hz
0.01
F001
4900
ECCE
PMU 1 Frequency Trigger High Frequency
20 to 70
Hz
0.01
F001
6100
Table B–10: MODBUS MEMORY MAP (Sheet 67 of 68)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...