GE Multilin
G60 Generator Protection System
2-3
2 PRODUCT DESCRIPTION
2.1 INTRODUCTION
2
2.1.2 SECURITY
The following security features are available:
•
Password security — Basic security present in the default offering of the product
•
EnerVista security — Role-based access to various EnerVista software screens and configuration elements. The fea-
ture is available in the default offering of the product and only in the EnerVista software.
•
CyberSentry security — Advanced security options available as a software option. When purchased, the options are
automatically enabled, and the default Password security and EnerVista security are disabled.
Changing the password, or any other setting, does not take the relay out of service. The relay is taken out of service when
a settings file is written to it.
a) ENERVISTA SECURITY
The EnerVista security management system is a role-based access control (RBAC) system that allows an administrator to
manage the privileges of multiple users. This allows for access control of UR devices by multiple personnel within a substa-
tion and conforms to the principles of RBAC as defined in ANSI INCITS 359-2004. The EnerVista security management
system is disabled by default to allow the administrator direct access to the EnerVista software after installation. It is recom-
mended that security be enabled before placing the device in service.
Basic password or enhanced CyberSentry security applies, depending on purchase.
b) PASSWORD SECURITY
Password security is a basic security feature present in the default offering of the product.
Two levels of password security are provided: command and setting.
The following operations are under command password supervision:
•
Changing the state of virtual inputs
•
Clearing the event records
•
Clearing the oscillography records
•
Changing the date and time
•
Clearing energy records
•
Clearing the data logger
•
Clearing the user-programmable pushbutton states
The following operations are under setting password supervision:
•
Changing any setting
•
Test mode operation
The G60 supports password entry from a local or remote connection. Local access is defined as any access to settings or
commands via the faceplate interface. This includes both keypad entry and the through the faceplate RS232 port. Remote
access is defined as any access to settings or commands via any rear communications port. This includes both Ethernet
and RS485 connections. Any changes to the local or remote passwords enables this functionality.
When entering a settings or command password via EnerVista or any serial interface, the user must enter the correspond-
ing connection password. If the connection is to the back of the G60, the remote password must be used. If the connection
is to the RS232 port of the faceplate, the local password applies.
Password access events are logged in the Event Recorder.
c) CYBERSENTRY SECURITY
CyberSentry Embedded Security is a software option that provides advanced security services. When this option is pur-
chased, the basic password security is disabled automatically.
CyberSentry provides security through the following features:
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...