5-132
G60 Generator Protection System
GE Multilin
5.4 SYSTEM SETUP
5 SETTINGS
5
k) PMU RECORDING
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT
PHASOR MEASUREMENT UNIT1
RECORDING PMU1
•
PMU 1 FUNCTION
: This setting enables or disables the recorder for PMU 1. The rate is fixed at the reporting rate set
within the aggregator (i.e., Aggregator 1).
•
PMU 1 NO OF TIMED RECORDS
: This setting specifies the number of timed records that are available for a given log-
ical PMU 1(4). The length of each record is equal to the available memory divided by the content size and number of
records. As the number of records is increased the available storage for each record is reduced. The relay supports a
maximum of 128 records in either timed or forced mode.
•
PMU 1 TRIGGER MODE
: This setting specifies what happens when the recorder uses its entire available memory
storage. Under the “Automatic Overwrite”, the last record is erased to facilitate new recording, when triggered. Under
the “Protected” selection, the recorder stops creating new records when the entire memory is used up by the old un-
cleared records.
•
PMU 1 TIMED TRIGGER POSITION
: This setting specifies the amount of pre-trigger data as a percent of the entire
record. This setting applies only to the timed mode of recording.
l) AGGREGATORS
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
When the protocol selection is set via the software or keypad, all aggregators whose protocol is not set to None will
be set to the last protocol saved (i.e., IEEE C37.118 or IEC 61850-90-5) to any aggregators, as both IEEE C37.118
and IEC 61850-90-5 simultaneous streaming of both R-SV values is not possible.
PATH: SETTINGS
SYSTEM SETUP
PHASOR MEASUREMENT UNIT
PMU AGGREGATOR 1
37.118 AGGR 1 CONFIG-
URATION
PMU 1
RECORDING
PMU 1 FUNCTION
DISABLE
Range: Enable, Disable
MESSAGE
PMU 1 NO OF TIMED
RECORDS: 10
Range: 2 to 128 in steps of 1
MESSAGE
PMU 1 TRIGGER MODE:
AUTOMATIC OVERWRITE
Range: Automatic Overwrite, Protected
MESSAGE
PMU 1 TIMED TRIGGER
POSITION: 10%
Range: 1 to 50% in steps of 1
PMU AGGREGATOR 1
PMU AGGREGATOR 1
PROTOCOL: NONE
Range: NONE, 37.118, 90-5
Default: NONE
MESSAGE
PMU AGGREGATOR 1:
IDCODE: 1
Range: 1 to 65534 in steps of 1
Default: 1
MESSAGE
PMU AGGREGATOR 1
INCLUDE PMU1: No
Range: No, Yes
Default: No
MESSAGE
37.118 AGGR 1
CONFIGURATION
See below.
MESSAGE
90-5 AGGR 1
CONFIGURATION
See below.
37.118 AGGR 1
CONFIGURATION
PMU AGGREGATOR 1
TCP PORT: 4712
Range: 1 to 65534
Default: 4712
MESSAGE
PMU AGGREGATOR 1
UDP PORT: 4713
Range: 1 to 65534
Default: 4713
MESSAGE
PMU AGGREGATOR 1
PDC CONTROL: Disabled
Range: Disabled, Enabled
Default: Disabled
NOTE
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...