5 SETTINGS
5.4 SYSTEM SETUP
5
5.4.4 BREAKERS
PATH: SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(4)
BREAKER 1
BREAKER 1
FUNCTION: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER1 PUSH BUTTON
CONTROL: Disabled
Range: Disabled, Enabled
MESSAGE
BREAKER 1 NAME:
Bkr 1
Range: up to 6 alphanumeric characters
MESSAGE
BREAKER 1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
MESSAGE
BREAKER 1 OPEN:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 BLK OPEN:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 CLOSE:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 BLK CLOSE:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
A/3P CLSD:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
A/3P OPND:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
B CLOSED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
B OPENED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
C CLOSED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1
Φ
C OPENED:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 Toperate:
0.070 s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BREAKER 1 EXT ALARM:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 ALARM
DELAY: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
MANUAL CLOSE RECAL1
TIME: 0.000
s
Range: 0.000 to 65.535 s in steps of 0.001
MESSAGE
BREAKER 1 OUT OF SV:
Off
Range: FlexLogic operand
MESSAGE
BREAKER 1 EVENTS:
Disabled
Range: Disabled, Enabled
Содержание Multilin g60
Страница 10: ...x G60 Generator Protection System GE Multilin TABLE OF CONTENTS INDEX ...
Страница 32: ...1 22 G60 Generator Protection System GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1 ...
Страница 130: ...3 68 G60 Generator Protection System GE Multilin 3 4 FIELD AND STATOR GROUND MODULES 3 HARDWARE 3 ...
Страница 160: ...4 30 G60 Generator Protection System GE Multilin 4 3 FACEPLATE INTERFACE 4 HUMAN INTERFACES 4 ...
Страница 486: ...5 326 G60 Generator Protection System GE Multilin 5 10 TESTING 5 SETTINGS 5 ...
Страница 518: ...6 32 G60 Generator Protection System GE Multilin 6 5 PRODUCT INFORMATION 6 ACTUAL VALUES 6 ...
Страница 532: ...7 14 G60 Generator Protection System GE Multilin 7 2 TARGETS 7 COMMANDS AND TARGETS 7 ...
Страница 538: ...8 6 G60 Generator Protection System GE Multilin 8 1 PHASE DISTANCE THROUGH POWER TRANSFORMERS 8 THEORY OF OPERATION 8 ...
Страница 748: ...D 10 G60 Generator Protection System GE Multilin D 1 IEC 60870 5 104 APPENDIX D D ...
Страница 760: ...E 12 G60 Generator Protection System GE Multilin E 2 DNP POINT LISTS APPENDIX E E ...