KEYPAD AND DISPLAY
GEK-106166E
DFF Digital Feeder Relay
57
9.5 SINGLE KEY OPERATIONS.
The DFF relay allows a simplified operation mode through the use of the
ENT
key. This mode allows access to
various relay information without the necessity to remove the transparent plastic cover. The operation mode consists
of repeatedly pressing the
ENT
key. To access this mode the relay must be in standby. The available information in
this operation mode is shown in the following table in the order that it is displayed.
MAGNITUDES
DESCRIPTION
Va
phase A primary voltage value (kV)
Vb
phase B primary voltage value (kV)
Vc
phase C primary voltage value (kV)
Vn
ground primary voltage value (kV)
Frequency
frequency value (Hz)
dF/Dt
rate of change of frequency (Hz/s)
PROTECTION STATUS
protection 'in' or 'out of service'
ACTIVE TABLE
active settings table
DATE/TIME
date and time
9.6 COMMUNICATIONS MENU.
The DFF relay includes a communications menu that can be accessed exclusively through the keypad. It is used to
select how the DFF will interact with the external environment.
The configuration unit is entered from the standby screen by entering a four digit numerical code (sequence of key
strokes). If the code is correct the LCD will show the configuration menu, if not the relay will return to the standby
screen.
The code is common to all DFF relays. It is not meant to be a password, but a simple measure of security to avoid
accidental manipulation of the configuration. The code is “
7” “1” “6” “9”,
which was selected because it is the
corresponding ASCII code for the initials GE (“G”=”71”, “E”=”69”). This is the step by step sequence of displays to
access the communications menu from the standby screen:
The settings are as follows: (to move in this group,
↑
/
↓
keys must be pressed).
•
NET BAUD RATE
: The baud rate used in the remote communication port at the rear. The possible values for
setting are between 1,200 and 115,200 baud.
•
NET STOP BITS
: Number of bits added to each byte transmitted across the serial line (remote comm. port). It is
treated as a logical binary setting with the logical key
1/Y
for 1, and key
3/N
for 2.
•
LOCAL BAUD RATE:
The baud rate used in the local communication port at the front. The possible values for
setting are between 1,200 and 115,200 baud.
•
LOCAL STOP BITS
: Number of bits added to each byte transmitted across the serial line (local comm. port). It is
treated as a logical binary setting with the logical key
1/Y
for 1, and key
3/N
for 2.
•
LOCAL SETTINGS
: Setting which enables/disables the settings change via local communication.
DFF
GENERAL ELECTRIC
*
**
***
7
→
1
→
6
→
9
→
NET BAUD RATE
Содержание Multilin DFF
Страница 5: ...TABLE OF CONTENTS 4 DFF Digital Feeder Relay GEK 106166E ...
Страница 25: ...EQUIPMENT CONFIGURATION 24 DFF Digital Feeder Relay GEK 106166E ...
Страница 29: ...TECHNICAL CHARACTERISTICS 28 DFF Digital Feeder Relay GEK 106166E ...
Страница 43: ...ACCEPTANCE TESTS 42 DFF Digital Feeder Relay GEK 106166E ...
Страница 45: ...KEYPAD AND DISPLAY 44 DFF Digital Feeder Relay GEK 106166E ...
Страница 60: ...FIGURES GEK 106166E DFF Digital Feeder Relay 59 10 FIGURES ...
Страница 61: ...FIGURES 60 DFF Digital Feeder Relay GEK 106166E Figure 1 External Connections for DFF1000 model ...
Страница 62: ...FIGURES GEK 106166E DFF Digital Feeder Relay 61 Figure 2 External Connections for DFF1001 model ...
Страница 63: ...FIGURES 62 DFF Digital Feeder Relay GEK 106166E Figure 3 External Connections for DFF1002 model ...
Страница 64: ...FIGURES GEK 106166E DFF Digital Feeder Relay 63 Figure 4 External Connections for DFF1003 model ...
Страница 65: ...FIGURES 64 DFF Digital Feeder Relay GEK 106166E Figure 5 External Connections for DFF 1012 model ...
Страница 66: ...FIGURES GEK 106166E DFF Digital Feeder Relay 65 Figure 6 External Connections for DFF 1011 model ...
Страница 67: ...FIGURES 66 DFF Digital Feeder Relay GEK 106166E Figure 7 Panel Mounting for 19 rack models ...
Страница 69: ...FIGURES 68 DFF Digital Feeder Relay GEK 106166E Figure 9 Dimensions diagram for 19 rack models ...
Страница 70: ...FIGURES GEK 106166E DFF Digital Feeder Relay 69 Figure 10 Dimensions Diagram for rack models ...
Страница 71: ...FIGURES 70 DFF Digital Feeder Relay GEK 106166E Figure 11 Front View for 19 rack models ...
Страница 72: ...FIGURES GEK 106166E DFF Digital Feeder Relay 71 Figure 12 Rear View for 19 rack model ...
Страница 73: ...FIGURES 72 DFF Digital Feeder Relay GEK 106166E Figure 13 Front View for rack models B2213F3 ...
Страница 74: ...FIGURES GEK 106166E DFF Digital Feeder Relay 73 Figure 14 Rear View for rack models B2213F2 ...