Upgrading Relay Firmware
745
Transformer Management Relay
Inter
faces
http://www.GEindustrial.com/multilin
4–21
GE Multilin
5. Select the target relay from the list of devices shown and click
Send
. If there is
an incompatibility, an error will occur informing the user of incompatibilities:
6. If there are no incompatibilities between the target device and the Setpoints
file, the data will be transferred to the relay. An indication of the percentage
completed will be shown in the bottom of the main menu.
Upgrading Relay Firmware
Description
To upgrade the 745 firmware, follow the procedures listed in this section. Upon
successful completion of this procedure, the 745 will have new firmware installed
with the original setpoints.
The latest firmware files are available from the GE Multilin website at
Saving Setpoints To A
File
Before upgrading firmware, it is very important to save the current 745 settings to a
file on your PC. After the firmware has been upgraded, it will be necessary to load
this file back into the 745.
Refer to
Downloading and Saving Setpoints Files
on page 4–17 for details on saving
relay setpoints to a file.
Loading New Firmware
Loading new firmware into the 745 flash memory is accomplished as follows:
1. Connect the relay to the local PC and save the setpoints to a file as shown in
Downloading and Saving Setpoints Files
2. Select the
Communications > Update Firmware
menu item.
3. The following warning message will appear. Select
Yes
to proceed or
No
the
cancel the process.
Do not proceed unless you have saved the current
setpoints
.
4. An additional message will be displayed to ensure the PC is connected to the
relay front port, as the 745 cannot be upgraded via the rear RS485 ports.