Hardware Interface
745
Transformer Management Relay
Inter
faces
http://www.GEindustrial.com/multilin
4–3
GE Multilin
the front panel display is sequentially displaying information about each
element that has detected an abnormal condition.
b) System Status Indicators
•
TRANSFORMER DE-ENERGIZED
: The Transformer De-Energized LED
indicator is on when the energization inhibit feature has detected that the
transformer is de-energized. The indicator is on if the Energization Inhibit
feature is detecting the transformer as de-energized
•
TRANSFORMER OVERLOAD
: The Transformer Overload LED indicator is on
when the Transformer Overload element has operated.
•
LOAD-LIMIT REDUCED
: The Load-Limit Reduced LED indicator is on when the
adaptive harmonic factor correction feature is detecting enough harmonic
content to reduce the load rating of the transformer. The indicator is on if
S2
SYSTEM SETUP
!"
HARMONICS
!
HARMONIC DERATING ESTIMATION
is “Enabled” and
the harmonic derating function is below 0.96.
•
SETPOINT GROUP 1(4)
: These indicators reflect the currently active setpoint
group. The indicators flash when the corresponding setpoint group is being
edited.
c) Output Status Indicators
•
TRIP
: The Trip LED is on when any output relay selected to be of the
Trip
type
has operated.
•
ALARM
: The Alarm LED is on when any output relay selected to be of the
Alarm
type has operated.
•
PICKUP
: The Pickup LED is on when any element has picked up. With this
indicator on, the front panel display is sequentially displaying information about
each element that has picked up.
•
PHASE A (C)
: The Phase A(C) LED is on when Phase A(C) is involved in the
condition detected by any element that has picked up, operated, or is now in a
latched state waiting to be reset.
•
Ground
: The Ground LED is on when ground is involved in the condition
detected by any element that has picked up, operated, or is now in a latched
state waiting to be reset.
Program Port
Use the front panel program port for RS232 communications with the 745. As
described in
RS232 Front Panel Program Port
on page 3–14, all that is required is a
connection between the relay and a computer running enerVista 745 Setup. For
continuous monitoring of multiple relays, use the COM1 RS485/RS422 port or the
COM2 RS485 port.
Keypad
a) Description
The 745 display messages are organized into main menus, pages, and sub-pages.
There are three main menus labeled Setpoints, Actual Values, and Target Messages.
Pressing the
MENU
key followed by the
MESSAGE
%
key scrolls through the three main
menu headers, which appear in sequence as follows:
SETPOINTS
[
!
]
ACTUAL VALUES
[
!
]
TARGET MESSAGES
[
!
]