![GE Multilin 489 Скачать руководство пользователя страница 146](http://html.mh-extra.com/html/ge/multilin-489/multilin-489_instruction-manual_123013146.webp)
5–36
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETPOINTS
•
ENABLE VOLTAGE RESTRAINT:
“Yes”
•
VOLTAGE LOWER LIMIT
: 10%
•
Phase-Phase Voltage / Rated Phase-Phase Voltage = 0.4 p.u. V
The voltage restrained phase overcurrent pickup level is calculated as follows:
(EQ 5.9)
The 489 phase overcurrent restraint voltages and restraint characteristic are shown below.
FIGURE 5–2: Voltage Restraint Characteristic
5.6.6
Negative Sequence
PATH: SETPOINTS
ZV
S5 CURRENT ELEM.
ZV
NEGATIVE SEQUENCE
Pickup
vrest
Phase OC Pickup Voltage Rest. Pickup Multiplier CT
×
×
=
2 0.4
×
(
)
CT
×
=
0.8 CT
×
=
808792A4.CDR
Phase-Phase Voltage / Rated Phase-Phase Voltage
Curve
Pickup
Multiplier
0
0
0.1
0.2
0.3
0.4
0.5
0.6
0.7
0.8
0.9
1
0.1
0.2
0.4
0.5
0.6
0.7
0.8
0.9
1
0.3
CURRENT
VOLTAGE
IA
Vab
IB
Vbc
IC
Vca
Phase Overcurrent Restraint Voltages:
1 NEGATIVE
[
Z
]
SEQUENCE
NEGATIVE SEQUENCE
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM
RELAYS (2-5): ---5
Range: Any combination of Relays 2 to
5
MESSAGE
NEG. SEQUENCE ALARM
PICKUP: 3% FLA
Range: 3 to 100% FLA in steps of 1
MESSAGE
NEGATIVE SEQUENCE
ALARM DELAY: 0.5 s
Range: 0.1 to 100.0 s in steps of 0.1
MESSAGE
NEGATIVE SEQUENCE
ALARM EVENTS: Off
Range: On, Off
MESSAGE
NEGATIVE SEQUENCE
O/C TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP
RELAYS (1-4): 1---
Range: Any combination of Relays 1 to
4
MESSAGE
NEG. SEQUENCE O/C
TRIP PICKUP: 8% FLA
Range: 3 to 100% FLA in steps of 1
MESSAGE
NEG. SEQUENCE O/C
CONSTANT K: 1
Range: 1 to 100 in steps of 1
MESSAGE
NEG. SEQUENCE O/C
MAX. TIME: 1000 s
Range: 10 to 1000 s in steps of 1