CHAPTER 5: SETPOINTS
489 GENERATOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–9
5.2
S1 489 Setup
5.2.1
Passcode
PATH: SETPOINTS
Z
S1 489 SETUP
Z
PASSCODE
A passcode access security feature is provided with the 489. The passcode is defaulted to
“0” (without the quotes) at the time of shipping. Passcode protection is ignored when the
passcode is “0”. In this case, the setpoint access jumper is the only protection when
programming setpoints from the front panel keypad and setpoints may be altered using
the RS232 and RS485 serial ports without access protection. If however, the passcode is
changed to a non-zero value, passcode protection is enabled. The access jumper must be
installed and the passcode must be entered, to program setpoints from the front panel
keypad. The passcode must also be entered individually from each serial communications
port to gain setpoint programming access from that port.
The
ENTER PASSCODE FOR ACCESS
setpoint is seen only if the passcode is not 0 and
SETPOINT ACCESS
is “Restricted”. The
SETPOINT ACCESS
and
CHANGE PASSWORD
setpoints
are seen only if the passcode is 0 and the
SETPOINT ACCESS
is “Permitted”.
To enable passcode protection on a new relay, follow the procedure below:
Z
Press
ENTER
then
MESSAGE DOWN
until
CHANGE PASSCODE
message is displayed.
Z
Select
Yes
and follow directions to enter a new passcode 1 to 8 digits in
length.
Once a new passcode (other than “0”) is programmed, it must be entered to gain setpoint
access whenever setpoint access is restricted. Assuming that a non-zero passcode has
been programmed and setpoint access is restricted, then selecting the passcode subgroup
causes the
ENTER PASSCODE AGAIN
message to appear.
Z
Enter the correct passcode. A flash message will advise if the code is
incorrect and allow a retry. If it is correct and the setpoint access jumper
is installed, the
SETPOINT ACCESS: Permitted
message appears.
Setpoints can now be entered.
Z
Exit the passcode message with the
ESCAPE
key and program the
appropriate setpoints.
If no keypress occurs for 30 minutes, access will be disabled and the
passcode must be re-entered. Removing the setpoint access jumper or
setting
SETPOINT ACCESS
to
Restricted
also disables setpoint access
immediately.
If a new passcode is required, gain setpoint access as follows:
PASSCODE
[
Z
]
ENTER PASSCODE FOR
ACCESS:
Range: 1 to 8 numeric digits
MESSAGE
SETPOINT ACCESS:
Permitted
Range: Permitted, Restricted
MESSAGE
CHANGE PASSCODE:
No
Range: No, Yes