CHAPTER 5: SETPOINTS
S2 PROTECTION
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5–19
•
THERMAL CAPACITY ALARM
: When the thermal capacity used exceeds the level set,
an alarm will be generated. This alarm can be assigned to a dedicated auxiliary relay.
•
OPEN CONTROL CIRCUIT TRIP
: In two-wire control applications where a constant
start signal is provided, the MM3 Motor Manager 3 should be configured to trip on an
open control circuit. An open control circuit occurs when feedback on contactor
status (terminal 55) stays open when a start operation is executed. This condition may
occur if a control wiring problem develops or because of an auxiliary contact failure.
The
OPEN CONTROL CIRCUIT TRIP
setpoint should be used in conjunction with the
RESET ALARMS USING RESET KEY
function.
•
RESET ALARMS USING RESET KEY
: The MM3 Motor Manager 3 will now allow the
acceleration alarm, open control circuit alarm, motor greasing, contactor inspection
and motor stopped time alarms to be reset using the faceplate RESET key. All other
alarms will reset when the alarm condition clears.
5.3.4
Load
Protection
PATH: S2 PROTECTION
ÖØ
LOAD PROTECTION
] LOAD PROTECTION
]
UNDERPOWER ALARM
LEVEL:
OFF kW
Range: 0.2 to 1100.0 kW or OFF in
steps of 0.1
UNDERPOWER ALARM
DELAY: 10 s
Range: 1 to 60 s in steps of 1
UNDERPOWER TRIP
LEVEL:
OFF kW
Range: 0.2 to 1100.0 kW or OFF in
steps of 0.1
UNDERPOWER TRIP
DELAY: 10 s
Range: 1 to 60 s in steps of 1
ACCELERATION TIME
ALARM: OFF s
Range: 0.5 to 125.0 s or OFF in steps of
0.5
ACCELERATION TIME
TRIP:
OFF s
Range: 0.5 to 125.0 s or OFF in steps of
0.5
LOAD INCREASE ALARM:
OFF %FLC
Range: 10 to 130% FLC or OFF in steps
of 1
UNDERCURRENT ALARM
LEVEL: OFF %FLC
Range: 10 to 100% FLC or OFF in steps
of 1
UNDERCURRENT ALARM
DELAY:
10 s
Range: 1 to 60 s in steps of 1
UNDERCURRENT TRIP:
LEVEL: OFF %FLC
Range: 10 to 100% FLC or OFF in steps
of 1
UNDERCURRENT TRIP
DELAY: 10
s
Range: 1 to 60 s in steps of 1
STALLED ROTOR TRIP
LEVEL: OFF
Range: 1.15 to 4.50
×
FLC or OFF in
steps of 0.05
STALLED ROTOR TRIP
DELAY:
3.0 s
Range: 0.5 to 5.0 s in steps of 0.5
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...