5–6
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S1 CONFIGURATION
CHAPTER 5: SETPOINTS
5.2.3
Starter
PATH: S1 CONFIGURATION
ÖØ
STARTER
The starter settings are programmed as follows:
•
STARTER TYPE
: Selects a type according to the configuration that the MM3 Motor
Manager 3 is controlling. This will determine the control logic used for contactor a and
contactor B start and stop sequences. See
description of each starter type.
The following starter types are available: OFF, FV NON-REVERSING, FV REVERSING, WYE
DELTA OPN TRANS, TWO SPEED, INVERTER, SLIP RING, AUTOTRANS OPN TRANS, PART
WINDING, WYE DELTA CLS TRANS, AUTOTRANS CLS TRANS, DUTY/STANDBY, and SOFT
STARTER.
•
CHANGE OVER CURRENT
: This setting appears only when the
STARTER TYPE
has been
selected as “WYE DELTA OPN TRNS” or “WYE DELTA CLS TRANS”. Before the
CHANGE
OVER CURRENT
comes into effect on a wye delta start, a minimum of 25% of the
CHANGE OVER TIME
must have expired. After 25% of the time has expired and the
average of the three phase currents has dropped below the
CHANGE OVER CURRENT
value, the transition from wye (contactor A) to delta (contactor B) will occur. If this
setpoint is “OFF”, 100% of the
CHANGE OVER TIME
must expire for the wye to delta
transition to occur.
•
CHANGE OVER TIME
: This setting appears only if
STARTER TYPE
is set as “WYE DELTA
OPN TRNS” or “WYE DELTA CLS TRANS”. See the
CHANGE OVER CURRENT
setpoint
above for operation.
•
TRANSFER TIME
: This setting appears only if
STARTER TYPE
is set as “FV REVERSING” or
“TWO SPEED”. With two-speed starters, this delay is required when the motor is
switched from high speed (contactor B) to low speed (contactor A). The delay starts
] STARTER
]
STARTER TYPE:
OFF
Range: see below
CHANGE OVER CURRENT:
1.5 xFLC
Range: 1.0 to 5.0
×
FLC or OFF in steps
of 0.1
CHANGE OVER TIME:
30 s
Range: 1 to 100 s in steps of 1
TRANSFER TIME:
10 s
Range: 0 to 125 s in steps of 1
HIGH SPEED START
BLOCK: DISABLE
Range: Enable, Disable
RAMP UP TIME:
5 s
Range: 1 to 125 s in steps of 1
RAMP DOWN TIME:
5 s
Range: 1 to 125 s in steps of 1
STAGE ONE SHORTING
TIME: 5 s
Range: 1 to 125 s in steps of 1
CONTACTOR SEQUENCE:
1S-2S
Range: 1S-2S, 2S-1S
CHANGE OVER TIME:
5 s
Range: 0 to 125 s in steps of 1
STARTS PER HOUR:
5
Range: 1 to 40 starts/hour or OFF in
steps of 1
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...