CHAPTER 4: SOFTWARE
CHASSIS MOUNT UNITS
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
4–15
4.4
Chassis Mount Units
4.4.1
Description
MM3 Motor Manager 3 chassis mount units no longer support automatic baud rate linking.
The default communication settings are 9600 baud, 8 data bits, one stop bit, no parity. It is
necessary to initially communicate with these settings and change them one at a time.
After each change the master must be changed to match the communication setting
change in the MM3 Motor Manager 3.
4.4.2
Setting the
Baud Rate and
Parity
Z
Assume your system communicates at 19200 baud and even
parity.
Z
Use EnerVista MM3 Setup to establish communications with the
chassis mount MM3 Motor Manager 3 at 9600 baud and no parity.
Z
Select the
Communication > Set Slave Address
menu item and
follow the on-screen instructions to store the communication
address of the MM3 Motor Manager 3.
Z
When completed, select
OK
to exit.
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...