2–36
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
STARTER TYPES
CHAPTER 2: INSTALLATION
Figure 2-27: Duty/Standby Starter
2.4.13 Soft Starter
When the RUN contact closes the soft starter ramps up the motor to the programmed
speed. When the RUN contact opens, the soft starter ramps down the motor to a stop.
To program the MM3 Motor Manager 3 for soft starter, set:
S1 CONFIGURATION
ÖØ
STARTER
Ö
STARTER TYPE
: SOFT STARTER
S1 CONFIGURATION
ÖØ
STARTER
ÖØ
RAMP UP TIME
: 1 to 125 sec.
S1 CONFIGURATION
ÖØ
STARTER
ÖØ
RAMP DOWN TIME
: 1 to 125 sec.
S3 PROCESS
Ö
PROGRAMMABLE INPUTS
ÖØ
INTERLOCK INPUT 10
: Bypass Contact
S4 CONTROL
ÖØ
AUX 1 RELAY CONFIG
Ö
AUX RELAY 1 FUNCTION
: Soft Starter Bypass
The
RAMP UP TIME
and
RAMP DOWN TIME
setpoints appear when
starter type
has been
selected as “SOFT STARTER”. See the MM3 Motor Manager 3 sequence below for details on
functionality.
Start:
1.
Start command received by the MM3 Motor Manager 3 (serial, switch input or
faceplate).
2.
Close and maintain contactor A output relay – provide power to the soft
starter.
3.
Wait for one second.
GE POWER MANAGEMENT
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...