CHAPTER 2: INSTALLATION
STARTER TYPES
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
2–29
Figure 2-23: Autotransformer Closed Transition Three Winding
2.4.9
Part Winding
Starter
To program the MM3 Motor Manager 3 for part winding starter, set:
S1 CONFIGURATION
ÖØ
STARTER
Ö
STARTER TYPE
: PART WINDING
S1 CONFIGURATION
ÖØ
STARTER
ÖØ
STAGE ONE SHORTING TIME
: 1 to 125 sec.
The
STAGE ONE SHORTING TIME
setpoint appears when the
STARTER TYPE
is selected as
“PART WINDING”. This is the time delay from the closure of contactor A until the closure of
contactor B.
The functionality of this starter is currently under review.
Start sequence:
1.
Start command received by the MM3 Motor Manager 3 (serial, switch input or
faceplate).
2.
Close and maintain contactor A output relay.
3.
Wait for the time set in the
STAGE ONE SHORTING TIME
setpoint.
4.
Close and maintain contactor B output relay.
Stop/trip sequence:
NOTE
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...