9–2
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
CONTROL WIRE APPLICATIONS
CHAPTER 9: APPLICATIONS
Figure 9-1: Two-wire Control
9.1.2
HOA Two-wire
Hand / Two-
wire Auto
This control scheme is used when it is desirable to operate the starter manually and
automatically. In the Hand position, the starter coil is energized immediately. In the auto
position, the starter is energized by the maintained PLC contact. When the PLC contact
opens, the motor stops.
To program the MM3 Motor Manager 3 for two-wire hand / two-wire auto control, set:
S3 PROCESS
Ö
PROGRAMMABLE INPUTS
Ö
INTERLOCK INPUT 1
: “TWO WIRE CONTROL”
S3 PROCESS
ÖØ
STOP CONFIGURATION
ÖØ
FACEPLATE STOP
: “LATCHED”
The
INTERLOCK INPUT 1
setpoint was chosen to match the wiring diagram provided. Any of
the available Interlocks 1 through 10 could be programmed for two-wire control.
Hand operation:
• In the hand position, the motor will run.
• Pressing the STOP key causes a latched trip. The motor cannot be restarted until
RESET is pressed.
Off operation:
• In the off position, the motor will stop.
GE POWER MANAGEMENT
NOTE
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...