CHAPTER 5: SETPOINTS
S5 MONITORING
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5–35
5.6
S5 Monitoring
5.6.1
Plant
Condition
PATH: S5 MONITORING
Ö
PLANT CONDITION
The plant condition settings are programmed as follows:
•
DRIVE GREASING INTERVAL
: Enter the interval at which the motor bearings must be
lubricated. When the motor running time exceeds this setpoint, a motor greasing
interval alarm is generated. Use the
S1 CONFIGURATION
ÖØ
STATISTICS
Ö
CLEAR
TIMERS
setpoint to clear the motor running hours. If this feature is not required. set this
setpoint to “OFF”.
•
CONTACTOR INSPECTION
: Enter the interval at which the contactor contacts must be
inspected for wear. When the
NUMBER OF STARTS
counter exceeds this setpoint, a
contactor inspection interval alarm is generated. Use the
S1 CONFIGURATION
ÖØ
STATISTICS
ÖØ
CLEAR COUNTERS
setpoint to clear the
NUMBER OF STARTS
counter. If
this feature is not required set this setpoint to “OFF”.
•
MAX DRIVE STOPPED TIME
: Enter the maximum interval that the motor can be left not
running. When the motor stopped time exceeds this setpoint, a maximum motor
stopped time alarm is generated. Start the motor to clear the motor stopped time. If
this feature is not required set this setpoint to “OFF”.
] PLANT CONDITION
]
DRIVE GREASING
INTERVAL: OFF hrs
Range: 100 to 50000 hours or OFF in
steps of 100
CONTACTOR INSPECTION
OFF x 1000 OPS
Range: 1000 to 10000000 operations
or OFF in steps of 1000
MAX DRIVE STOPPED
TIME: OFF hrs
Range: 10 to 10000 hours or OFF in
steps of 10
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...