5–32
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S4 CONTROL
CHAPTER 5: SETPOINTS
5.5.2
Auxiliary Relay
Configuration
PATH: S4 CONTROL
ÖØ
AUX RELAY 1(2) CONFIG
The MM3 Motor Manager 3 has two auxiliary programmable output relays. These two
outputs can be assigned any of the functions listed below. Once a function has been
assigned to one of the auxiliary relays it cannot be assigned to the other with the
exception of the serial control function which can be set to both auxiliary relays.
The setpoints listed under the
AUX RELAY 2 CONFIG
page operate in the same manner as
the setpoints shown below for
AUX RELAY 1 CONFIG
.
The auxiliary relay configuration settings are programmed as follows:
•
AUX RELAY 1 FUNCTION
: The dual form-C auxiliary relay 1 can be configured to
activate on various conditions as described below:
• “SERIAL CONTROL”: Auxiliary relay 1 can be energized or de-energized via the serial
port.
• “TRIPS”: Auxiliary relay 1 will be energized when the MM3 Motor Manager 3 is
tripped. Resetting the MM3 Motor Manager 3 will de-energize auxiliary relay 1.
• “ALARMS”: Auxiliary relay 1 will be energized while any alarm is present.
• “PRE CONTACTOR A”: Auxiliary relay 1 will energize when the MM3 Motor Manager 3
receives a start command. The contactor A relay will start the motor after the
delay specified in the
AUX RELAY 1 PRE START DELAY
setpoint. Auxiliary relay 1 will
de-energize after the
AUX RELAY 1 POST START DELAY
times out or when contactor
A de-energizes.
• “PRE CONTACTOR B”: Auxiliary relay 1 will energize when the MM3 Motor Manager 3
receives a start B command. The contactor B relay will start the motor after the
delay specified in the
AUX RELAY 1 PRE START DELAY
setpoint. Auxiliary relay 1 will
de-energize after the
AUX RELAY 1 POST START DELAY
times out or when contactor
B de-energizes. Pre contactor B is active for the two-speed, full-voltage reversing,
and duty/standby starter types only.
] AUX RELAY 1 CONFIG
]
AUX RELAY 1 FUNCTION:
SERIAL CONTROL
Range: see below
AUX RELAY 1 DELAY
5 s
Range: 0 to 125 s in steps of 1
AUX RELAY 1 PRE
START DELAY: 5 s
Range: 0 to 900 s in steps of 1
AUX RELAY 1 POST
START DELAY: OFF s
Range: 0 to 125 s or OFF in steps of 1
ENERGIZE ON MOTOR
START DELAY: 5 s
Range: 0 to 125 s or OFF in steps of 1
DE-ENERGIZE ON MOTOR
STOP DELAY: 5 s
Range: 0 to 125 s or OFF in steps of 1
AUX 1 OPERATION:
NON-FAILSAFE
Range: FAILSAFE, NON-FAILSAFE
DELAY CONTACTOR G/F
TRIP BY: 0 ms
Range: 0 to 1000 ms in steps of 100
NOTE
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...