CHAPTER 5: SETPOINTS
S3 PROCESS
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
5–29
•
ANALOG ALARM LOW DELAY
: The analog input scaled value must be less than the
ANALOG ALARM LOW LEVEL
for the time specified by this setpoint before an alarm will
occur.
•
ANALOG INPUT HIGH LEVEL
: If the analog input scaled value exceeds the level set by
this setpoint, an analog input high alarm will occur. The alarm level must be a value
between the
MINIMUM SCALE
and
MAXIMUM SCALE
values.
•
ANALOG INPUT HIGH DELAY
: The analog input scaled value must be greater than the
ANALOG ALARM HIGH LEVEL
for the time specified by this setpoint before an alarm will
occur.
•
ANALOG TRIP LOW LEVEL
: If the analog input scaled value drops below the level set
by this setpoint, an analog input low trip will occur. The trip level must be a value
between the
MINIMUM SCALE
and
MAXIMUM SCALE
values.
•
ANALOG TRIP LOW OVERRIDE
: The analog level must reach a healthy state (greater
than trip level) after a start within the amount of time set by this setpoint. If the value
is 0, the analog level must be healthy when a start is initiated or an analog trip will
occur immediately. If set to “OFF”, the trip will occur if the analog level is unhealthy,
regardless if the motor is running or stopped.
•
ANALOG TRIP LOW DELAY
: The analog input scaled value must be less than the
ANALOG TRIP LOW LEVEL
for the time specified by this setpoint before a trip will occur.
•
ANALOG TRIP HIGH LEVEL
: If the analog input scaled value exceeds the level set by
this setpoint, an analog input high trip will occur. The trip level must be a value
between the
MINIMUM SCALE
and
MAXIMUM SCALE
values.
•
ANALOG TRIP HIGH OVERRIDE
: The analog level must reach a healthy state (less than
trip level) after a start within the amount of time set by this setpoint. If the value is 0,
the analog level must be healthy when a start is initiated or an analog trip will occur
immediately. If the value is set to “OFF”, the trip will occur if the analog level is
unhealthy, regardless if the motor is running or stopped.
•
ANALOG TRIP HIGH DELAY
: The analog input scaled value must be above the
ANALOG
TRIP HIGH LEVEL
for the time specified by this setpoint before a trip will occur.
5.4.5
Analog Output
PATH: S3 PROCESS
ÖØ
ANALOG OUTPUT
The
ANALOG OUTPUT TYPE
can be set to one of the following values and associated range.
•
“MOTOR LOAD”: Motor current as a percentage of full load current (FLC). The range is
from 0 to 200% of motor full load current.
•
“AVERAGE PHASE AMPS”: The range is from 0 to 100% of the
CT PRIMARY AMPS
setpoint.
•
“THERMAL CAPACITY”: Motor thermal capacity used. The range is from 0 to 100%.
] ANALOG OUTPUT
]
ANALOG OUTPUT TYPE:
NOT USED
Range: see below
ANALOG OUTPUT
FORCE: OFF %
Range: 0 to 100% or OFF in steps of 1
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...