5–28
MM3 MOTOR MANAGER 3 – INSTRUCTION MANUAL
S3 PROCESS
CHAPTER 5: SETPOINTS
5.4.4
Analog Input
PATH: S3 PROCESS
ÖØ
ANALOG INPUT
The analog input settings are programmed as follows:
•
ANALOG INPUT NAME
and
ANALOG INPUT UNIT
: The MM3 Motor Manager 3 allows
the user to program user defined names for the analog input and units. To store the
name, use the VALUE keys to change cursor to the desired letter or number, then press
STORE. This stores the character and moves the cursor to the next position. Repeat
this sequence until the entire message has been entered. One of the characters is a
blank space which can be used if no new character is required. If the cursor is at the
end of the message, pressing STORE causes the cursor to wrap around to the first
position. This message will now appear on any actual values message relating to
analog input.
•
MINIMUM SCALE
and
MAXIMUM SCALE
: The analog input can be scaled to user-
defined values. Minimum (4 mA) and maximum (20 mA) scale values must be specified
with these setpoints.
•
ANALOG ALARM LOW LEVEL
: If the analog input scaled value drops below the level
set by this setpoint, an analog input low alarm will occur. The alarm level must be a
value between the
MINIMUM SCALE
and
MAXIMUM SCALE
values.
] ANALOG INPUT
]
ANALOG INPUT NAME:
ANALOG INPUT
Range: 20 alphanumeric characters
ANALOG INPUT UNIT:
UNITS
Range: 20 alphanumeric characters
MINIMUM SCALE:
4 mA:
0
Range: 0 to 20000 in steps of 10
MAXIMUM SCALE:
20 mA: 1000
Range: 0 to 20000 in steps of 10
ANALOG ALARM LOW
LEVEL:
OFF
Range: 1 to 20000 or OFF in steps of 1
ANALOG ALARM LOW
DELAY: 5 s
Range: 1 to 600 s or OFF in steps of 1
ANALOG ALARM HIGH
LEVEL:
OFF
Range: 1 to 20000 or OFF in steps of 1
ANALOG ALARM HIGH
DELAY:
5 s
Range: 1 to 600 s or OFF in steps of 1
ANALOG TRIP LOW
LEVEL: OFF
Range: 1 to 20000 or OFF in steps of 1
ANALOG TRIP LOW
OVERRIDE: 5 s
Range: 0 to 600 s or OFF in steps of 1
ANALOG TRIP LOW
DELAY: 5 s
Range: 1 to 600 s or OFF in steps of 1
ANALOG TRIP HIGH
LEVEL: OFF
Range: 1 to 20000 or OFF in steps of 1
ANALOG TRIP HIGH
OVERRIDE: 5 s
Range: 0 to 600 s or OFF in steps of 1
ANALOG TRIP HIGH
DELAY: 5 s
Range: 1 to 600 s or OFF in steps of 1
Содержание MM3
Страница 8: ...vi MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 11: ...CHAPTER 1 INTRODUCTION OVERVIEW MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL 1 3 Figure 1 1 Functional block diagram ...
Страница 18: ...1 10 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL TECHNICAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 80: ...4 18 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL CHASSIS MOUNT UNITS CHAPTER 4 SOFTWARE ...
Страница 124: ...5 44 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL S7 TESTING CHAPTER 5 SETPOINTS ...
Страница 198: ...8 54 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL MODBUS MEMORY MAP CHAPTER 8 COMMUNICATIONS ...
Страница 220: ...10 14 MM3 MOTOR MANAGER 3 INSTRUCTION MANUAL GE MULTILIN WARRANTY CHAPTER 10 MISCELLANEOUS ...