CHAPTER 6: SPECIFICATIONS
TESTING AND CERTIFICATION
MM200 MOTOR MANAGEMENT SYSTEM – QUICK START GUIDE
31
RS485 PORT
Port: ........................................................................... opto-isolated
Baud rates:............................................................. up to 115 kbps
Protocol: .................................................................. Modbus RTU, half-duplex
Maximum distance: ........................................... 1200 m
Isolation:.................................................................. 2 kV
Testing and certification
TYPE TESTS (TEST NOT PERFORMED FOR AC PSU)
Test
Reference Standard
Test Level
Dielectric voltage withstand
2.3KV
Impulse voltage withstand
EN60255-5
5KV
Damped Oscillatory
IEC61000-4-18IEC60255-22-1
2.5KV CM, 1KV DM
Electrostatic Discharge
EN61000-4-2/IEC60255-22-2
Level 4
RF immunity
EN61000-4-3/IEC60255-22-3
Level 3
Fast Transient Disturbance
EN61000-4-4/IEC60255-22-4
Class A
Surge Immunity
EN61000-4-5/IEC60255-22-5
Level 3
Conducted RF Immunity
EN61000-4-6/IEC60255-22-6
Level 3
Power Frequency Immunity
EN61000-4-7/IEC60255-22-7
Class A
Voltage interruptionand Ripple DC IEC60255-11
15% ripple, 200ms interupts
Radiated & Conducted Emissions
CISPR11 /CISPR22/ IEC60255-25 Class A
Sinusoidal Vibration
IEC60255-21-1
Class 1
Shock & Bump
IEC60255-21-2
Class 1
Siesmic
IEC60255-21-3
Class 2
Power magnetic Immunity
IEC61000-4-8
Level 5
Pulse Magnetic Immunity
IEC61000-4-9
Level 4
Damped Magnetic Immunity
IEC61000-4-10
Level 4
Voltage Dip & interruption
IEC61000-4-11
0,40,70% dips,250/300cycle
interrupts
Damped Oscillatory
IEC61000-4-12
2.5KV CM, 1KV DM
Voltage Ripple
IEC61000-4-17
15% ripple
Ingress Protection
IEC60529
IP20 (base unit) , IP54
(Control Panel)
Environmental (Cold)
IEC60068-2-1
-25C 16 hrs
Environmental (Dry heat)
IEC60068-2-2
70C 16hrs
Relative Humidity Cyclic
IEC60068-2-30
6day variant 2
UL508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
UL1053
e83849 NKCR
Содержание MM200
Страница 21: ...16 MM200 MOTOR MANAGEMENT SYSTEM QUICK START GUIDE CONTROL PANEL CHAPTER 2 INSTALLATION...
Страница 31: ...26 MM200 MOTOR MANAGEMENT SYSTEM QUICK START GUIDE CHAPTER 5 COMMUNICATIONS INTERFACES...
Страница 39: ...34 MM200 MOTOR MANAGEMENT SYSTEM QUICK START GUIDE ENVIRONMENTAL SPECIFICATIONS CHAPTER 6 SPECIFICATIONS...
Страница 41: ...36 MM200 MOTOR MANAGEMENT SYSTEM QUICK START GUIDE EXAMPLE OF AN MM200 ORDER CODE CHAPTER 7 MM200 ORDER CODES...