GEK-98846A
62
6. ACCEPTANCE TESTS
6.1 FUNCTIONAL TESTS
Slowly apply 2200 volts RMS for the initial test and 1600 volts for following periodic
tests, between all short-circuited terminals (except the "A1" terminal connected to ground)
and the ease for 1 second.
6.2 ACCEPTANCE TESTS
Necessary equipment:
* 3 Multiamp units, or in their place 3 voltage sources, 3 current sources
* A continuous voltage source
* A stopwatch
* A multimeter
* A latching relay which simulates a breaker
Jumpers and switches placed over the extensors are used to simulate closing
exterior contacts. Combinations of resistance and voltmeters are used to observe the
active signals across the auxiliary relays in the following form:
Relay deenergized:
Contact open
Relay energized:
Contact closed
Connect the relay in accordance with the scheme in figure 16.
6.2.1 INITIAL CONFIGURATION
Apply power to the relay and, using the keyboard, enter the password '0186' with
asterisks appearing on the display.
Once the password has been entered, the following will be momentarily displayed
on the monitor
SYSTEM
CONFIGURATION
rapidly changing to:
MLP
GENERAL ELECTRIC
At this point the default settings configuration is:
- 2400 baud and 1 stop bit for remote communications
Содержание MLP1000
Страница 94: ...GEK 98846A 93 Figure 1 System diagram with MLP CPR and TTI ...
Страница 95: ...GEK 98846A 94 Figure 2 Case dimensions and drilling form 1 rack ...
Страница 96: ...GEK 98846A 95 Figure 3 1 External Connections MLP1000 ...
Страница 97: ...GEK 98846A 96 Figure 3 2 External Connections MLP1000 ...
Страница 99: ...GEK 98846A 98 Figure 3 4 External Connections MLP1000 ...
Страница 100: ...GEK 98846A 99 Figure 3 5 External Connections MLP2000 ...
Страница 101: ...GEK 98846A 100 Figure 3 6 External Connections MLP2000 ...
Страница 103: ...GEK 98846A 102 Figure 3 8 External Connections MLP2000 ...
Страница 104: ...GEK 98846A 103 Figure 3 9 External Connections MLP3000 ...
Страница 105: ...GEK 98846A 104 Figure 3 10 External Connections MLP3000 ...
Страница 107: ...GEK 98846A 106 Figure 3 12 External Connections MLP3000 ...
Страница 108: ...GEK 98846A 107 Figure 4 Protection Logic ...
Страница 109: ...GEK 98846A 108 Figure 5 1 Trip decision diagram ...
Страница 110: ...GEK 98846A 109 Figure 5 2 Trip decision diagram ...
Страница 111: ...GEK 98846A 110 Figure 5 3 Trip decision diagram ...
Страница 112: ...GEK 98846A 111 Figure 5 4 Trip decision diagram ...
Страница 113: ...GEK 98846A 112 Figure 6 1 Z1X protection scheme ...
Страница 114: ...GEK 98846A 113 Figure6 2 ACCZ2 Protection scheme ...
Страница 115: ...GEK 98846A 114 Figure7 LPU function diagram ...
Страница 116: ...GEK 98846A 115 Figure 8 1 ROD function logic ...
Страница 117: ...GEK 98846A 116 Figure 8 2 ROD function diagram ...
Страница 118: ...GEK 98846A 117 Figure 9 1 DD function logic ...
Страница 119: ...GEK 98846A 118 Figure 9 2 DD function diagram ...
Страница 120: ...GEK 98846A 119 Figure 10 1 FF function logic ...
Страница 121: ...GEK 98846A 120 Figure 10 2 FF function diagram ...
Страница 122: ...GEK 98846A 121 Figure 11 1 Recloser diagram ...
Страница 123: ...GEK 98846A 122 Figure 11 2 Recloser Diagram ...
Страница 124: ...GEK 98846A 123 Figure 11 3 Recloser Diagram ...
Страница 125: ...GEK 98846A 124 Figure 12 Fault selector ...
Страница 126: ...GEK 98846A 125 Figure 13 Menu Tree Diagram ...
Страница 127: ...GEK 98846A 126 Figure 14 MLP3000 Settings and data ...
Страница 128: ...GEK 98846A 127 Figure 15 Connection scheme for relay tests ...
Страница 129: ...GEK 98846A 128 Figure 16 Power swing diagram function ...
Страница 130: ...GEK 98846A 129 Figure 17 Mho Reactance characteristics of the MLP ...