2–14
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 2: INTRODUCTION
2.2.7
CPU
COMMUNICATIONS
RS232 port:........................................................1, front panel, non-isolated
RS485 ports:......................................................2, isolated together at 36 V
pk
Baud rates: ........................................................300, 1200, 2400, 4800, 9600, and 19200 (for RS485);
9600 (for RS232)
Parity: ...................................................................None, Odd, Even
Ethernet: .............................................................10Base-T RJ45 connector
Modbus TCP/IP
Version 2.0 / IEEE 802.3
MODBUS
Modbus: ..............................................................Modbus
®
RTU / half-duplex
DEVICENET
Baud rate: ..........................................................125K, 250K, 500K
MAC ID: ................................................................0 to 63 range
Connection type: ...........................................Explicit Messages, Poll I/O, Change Of State
ODVA certified
CLOCK
Accuracy:............................................................±5 minutes/month
Supercap backup life: .................................45 days when control power is off
2.2.8
Waveform Capture (Trace Memory)
SAMPLING FREQUENCY
Frequency:.........................................................720 samples per second for 60 Hertz system
600 samples per second for 50 Hertz system
ANALOG WAVEFORMS
Analog Waveforms:.......................................Phase currents Ia, Ib, Ic
Phase differential currents Ia Diff., Ib Diff., Ic Diff.
Ground Current
Phase voltages Van(Vab), Vbn, Vcn(Vcb)
DIGITAL WAVEFORMS
Digital Waveforms:........................................TRIP RELAY
AUX RELAY 2
AUX RELAY 3
ALARM RELAY
BLOCK START RELAY
SELF TEST RELAY
2.2.9
Testing
TYPE TESTING
The table below lists the 469 type tests:
Standard
Test Name
Level
EIA 485
RS485 Communications Test
32 units at 4000 ft.
GE
Digital
Energy
Temperature Cycling
–50°C / +80°C
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...