6–4
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 6: ACTUAL VALUES
6.2
A1 Status
6.2.1
Motor Status
PATH: ACTUAL VALUES
A1 STATUS
MOTOR STATUS
These messages describe the motor status at any given point in time. If the motor has
been tripped and the 469 has not yet been reset, the
MOTOR STATUS
value will be “Tripped”.
The
MOTOR THERMAL CAPACITY USED
reflects an integrated value of both the Stator and
Rotor Thermal Capacity Used. The values for
ESTIMATED TRIP TIME ON OVERLOAD
appear
whenever the 469 picks up on the overload curve.
6.2.2
Last Trip Data
PATH: ACTUAL VALUES
A1 STATUS
LAST TRIP DATA
MOTOR STATUS
[
]
MOTOR STATUS:
Stopped
Range: Tripped, Stopped, Starting,
Running, Overload
MESSAGE
MOTOR THERMAL
CAPACITY USED: 0%
Range: 0 to 100%
MESSAGE
ESTIMATED TRIP TIME
ON OVERLOAD: Never
Range: 0 to 10000 sec., Never
MESSAGE
MOTOR SPEED:
Low Speed
Range: HIgh Speed, Low Speed. Seen if
two speed motor is enabled
LAST TRIP
[
]
DATA
CAUSE OF LAST TRIP:
No Trip to Date
Range: see below
MESSAGE
TIME OF LAST TRIP:
09:00:00.00
Range: hour:min:sec
MESSAGE
DATE OF LAST TRIP:
Jan 01 1995
Range: Month Day Year
MESSAGE
MOTOR SPEED DURING
TRIP: Low Speed
Range: High Speed, Low Speed. Seen if
two-speed motor is enabled
MESSAGE
TACHOMETER
PreTrip: 3600 RPM
Range: 0 to 3600 RPM. Seen if a Digital
Input set as Tachometer.
MESSAGE
A:
0
B:
0
C:
0
A PreTrip
Range: 0 to 100000 A
MESSAGE
MOTOR LOAD:
0.00 x FLA PreTrip
Range: 0.00 to 20.00 x FLA
MESSAGE
CURRENT UNBALANCE
PreTrip: 0%
Range: 0 to 100%
MESSAGE
GROUND CURRENT
PreTrip: 0.00 Amps
Range: 0.0 to 5000.0 A. Not seen if
Ground CT is set to “None”.
MESSAGE
A:
0
B:
0
C:
0
A Diff.PreTrip
Range: 0 to 5000 A. Not seen if
Differential CT is set as None
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...