469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
CHAPTER 5: SETTINGS
5.13.3 Analog Input Diff 1-2
PATH: SETTINGS
S12 ANALOG I/O
ANALOG INPUT DIFF 1–2
NOTE
Note
This settings menu is seen only if Analog Inputs 1 and 2 are enabled. The
ANALOG IN DIFF 1-
2 TRIP LEVEL
and
ANALOG IN DIFF 1-2 ALARM LEVEL
settings are shown units of “%” if the
ANALOG IN DIFF 1-2 COMPARISON
is “%Diff” or in units defined by the
ANALOG INPUT 1 UNITS
settings if
ANALOG IN DIFF 1-2 COMPARISON
is “Abs Diff”.
This feature compares two analog inputs and activate alarms or trips based on their
difference, which can be an absolute difference in units or a percentage difference. The
second analog input (2 for 1-2) is used as the reference value for percentage calculations.
The comparison logic can also be selected as one input greater than the other (“1>2”) or
vice versa (“2>1”) or as absolute difference (“1<>2”). The compared analog inputs must be
programmed with the same units type prior to programming this feature.
ANALOG INPUT
[
]
DIFF 1-2
ANALOG IN DIFF 1-2:
Disabled
Range: Disabled, Enabled
MESSAGE
ANALOG IN DIFF 1-2
NAME: Analog 1-2
Range: 12 alphanumeric characters
MESSAGE
ANALOG IN DIFF 1-2
COMPARISON: % Diff
Range: % Diff, Abs. Diff
MESSAGE
ANALOG IN DIFF 1-2
LOGIC: 1<>2
Range: 1<>2, 1>2, 2>1
MESSAGE
ANALOG IN DIFF 1-2
ACTIVE: Always
Range: Always, Start/Run
MESSAGE
A/I DIFF 1-2 BLOCK
FROM START: 0 s
Range: 0 to 5000 s in steps of 1
MESSAGE
ANALOG IN DIFF 1-2
ALARM: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN ALARM RELAYS:
Alarm
Range: Alarm, Alarm & Auxiliary2,
Alarm & Aux2 & Aux3, Alarm &
Auxiliary3, Auxiliary2, Aux2 &
Aux3, Auxiliary3, None
MESSAGE
ANALOG IN DIFF 1-2
ALARM LEVEL: 10%
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 1-2
ALARM DELAY: 0.1 s
Range: 0.1 to 300.0 s in steps of 0.1
MESSAGE
ANALOG IN DIFF 1-2
EVENTS: Off
Range: On, Off
MESSAGE
ANALOG IN DIFF 1-2
TRIP: Off
Range: Off, Latched, Unlatched
MESSAGE
ASSIGN TRIP RELAYS:
Trip
Range: Trip, Trip & Auxiliary2, Trip &
Aux2 & Aux3 Trip & Auxiliary3
MESSAGE
ANALOG IN DIFF 1-2
TRIP LEVEL: 10%
Range: 0 to 500% in steps of 1 or
0 to 50000 Units in steps of 1
MESSAGE
ANALOG IN DIFF 1-2
TRIP DELAY: 0.1 s
Range: 0.1 to 300.0 s in steps of 0.1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...