CHAPTER 5: SETTINGS
469 MOTOR MANAGEMENT RELAY – INSTRUCTION MANUAL
5–71
5.8.4
Restart Block
PATH: SETTINGS
S7 MOTOR STARTING
RESTART BLOCK
The Restart Block feature may be used to ensure that a certain amount of time passes
between stopping a motor and restarting that motor. This timer feature may be very useful
for some process applications or motor considerations. If a motor is on a down-hole pump,
after the motor stops, the liquid may fall back down the pipe and spin the rotor backwards.
It would be very undesirable to start the motor at this time. In another scenario, a motor
may be driving a very high inertia load. Once the supply to the motor is disconnected, the
rotor may continue to turn for a long period of time as it decelerates. The motor has now
become a generator and applying supply voltage out of phase may result in catastrophic
failure.
NOTE
Note
The Restart Block feature is strictly a timer. The 469 does not sense rotor rotation.
RESTART
[
]
BLOCK
RESTART BLOCK:
Off
Range: On, Off
MESSAGE
RESTART BLOCK
TIME: 1 s
Range: 1 to 50000 s in steps of 1
Содержание Masoneilan 469 Series
Страница 4: ......
Страница 91: ...CHAPTER 3 INSTALLATION 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 3 27 3 2 14 2 Speed Motor Wiring ...
Страница 92: ...3 28 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 3 INSTALLATION ...
Страница 256: ...5 112 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 5 SETTINGS ...
Страница 298: ...6 42 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 6 ACTUAL VALUES ...
Страница 300: ...7 2 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 7 TESTING FIGURE 7 1 Secondary Injection Test Setup ...
Страница 319: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 7 HGF5C 808841A1 HGF8 808842A1 ...
Страница 321: ...CHAPTER 8 APPENDIX 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL 8 9 808712A1 CDR ...
Страница 330: ...8 18 469 MOTOR MANAGEMENT RELAY INSTRUCTION MANUAL CHAPTER 8 APPENDIX ...