COMMUNICATIONS GUIDE
MODBUS MEMORY MAP
469 MOTOR MANAGEMENT RELAY – COMMUNICATIONS GUIDE
29
02B2
Starts/hour block lockout time
0
60
1
minutes F1
0
02B3
Time between starts lockout time
0
500
1
minutes F1
0
02B4
Restart block lockout
0
50000
1
s
F1
0
02B5
Reserved
--
--
02CF
Reserved
DIGITAL
INPUTS
02D0
Access switch status
0
1
1
--
F131
0
02D1
Test switch status
0
1
1
--
F131
0
02D2
Starter switch status
0
1
1
--
F131
0
02D3
Emergency restart switch status
0
1
1
--
F131
0
02D4
Remote reset switch status
0
1
1
--
F131
0
02D5
Assignable switch #1 status
0
1
1
--
F131
0
02D6
Assignable switch #2 status
0
1
1
--
F131
0
02D7
Assignable switch #3 status
0
1
1
--
F131
0
02D8
Assignable switch #4 status
0
1
1
--
F131
0
02D9
Trip coil supervision
0
1
1
--
F132
0
02DA
Reserved
--
--
02DF
Reserved
LOSS OF
COMMS
02E0
Loss of Comms Port
0
1
1
--
F167
0
02E1
Reserved
--
--
02FB
Reserved
REAL TIME
CLOCK
02FC
Date (read only)
--
--
--
--
--
--
02FE
Time (read only)
--
--
--
--
--
--
CURRENT
METERING
0300
Phase A current
0
100000
1
A
F9
0
0302
Phase B current
0
100000
1
A
F9
0
0304
Phase C current
0
100000
1
A
F9
0
0306
Average phase current
0
100000
1
A
F9
0
0308
Motor load
0
2000
1
FLA
F3
0
0309
Current unbalance
0
100
1
%
F1
0
030A
Equivalent motor load
0
2000
1
FLA
F3
0
030B
Ground current
0
5000
1
A
F11
0
030D
Phase A differential current
0
5000
1
A
F1
0
030E
Phase B differential current
0
5000
1
A
F1
0
030F
Phase C differential current
0
5000
1
A
F1
0
0310
Reserved
0311
Reserved
--
--
031F
Reserved
Table 7: 469 MEMORY MAP (Sheet 11 of 90)
GROUP
ADDR
(HEX)
DESCRIPTION
MIN.
MAX.
STEP
VALUE
UNITS
FORMAT
CODE
DEFAULT