7.9
Thermocouple Inputs
YUAA reads temperature inputs from thermocouples with E, J, K, S, T, B, N, and R styles, and has open wire detection.
Source
I / O+
I / O-
Thermocouple
I / O+
I / O -
Thermocouple
Input
Supported TC Types and Temperature Ranges
TC Type
Min
Max
mV
-40
114
Min Temp (ºF)
Max Temp (ºF)
T
-328
752
K
-328
2501.6
J
-337.38
2192
E
-328
1832
S
-40
3214.4
B
32
3308
N
-454
2372
R
-58
3214.4
Burnout detection on the input is based on a periodic pulse of current forcing the open terminal voltage outside the
normal -40 to 95 mV region. Therefore, there may be a delay of up to 1 second from the time a sensor fails to when the
burnout is detected. When the input goes open, the input terminal voltage typically drops close to zero. If the thermocouple
sensor is hotter than the YUAA screw temperature, the reported temperature reading will report colder (since the TC had been
at a positive terminal input voltage). If the thermocouple sensor is colder than the YUAA screw temperature, the temperature
reading will momentarily report a warmer temperature, until the pulsed current source causes detection of the open circuit and
the behavior specified by the
ReportOpenTC
parameter is applied.
Burnout Detection is only enabled on E, J ,K, S, T, B, N and R styles of thermocouples. When the
ReportOpenTC
parameter
is set to Fail_Cold, the YUAA will report Extrapolated values from TC tables at -40 mV (Open TC threshold). When
ReportOpenTC
is set to Fail_Hot, the YUAA will report 2000 °C (3632 °F) depending on TempUnits selection. Burnout
detection is disabled on mv selection. Therefore, ± 312.5 mV can be read with mv type selection with healthy zone limited
from -40 mV to 114 mV.
192
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Содержание Mark VIeS
Страница 16: ...Notes 16 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 84: ...Notes 84 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 114: ...Notes 114 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 130: ...Notes 130 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 145: ...TRLYS1B Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 145 Public Information ...
Страница 153: ...TRLYS1D Circuits TMR YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 153 Public Information ...
Страница 157: ...TRLYS1F Terminal Board Wiring YDOA Discrete Output Modules GEH 6855_Vol_II System Guide 157 Public Information ...
Страница 210: ...210 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 226: ...Notes 226 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 284: ...Notes 284 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 369: ...JPDE Photo PDM Power Distribution Modules GEH 6855_Vol_II System Guide 369 Public Information ...
Страница 396: ...JGND Mounting 396 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 440: ...Notes 440 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 476: ...Notes 476 GEH 6855_Vol_II GEH 6855_Vol_II Mark VIeS Functional Safety Systems Volume II Public Information ...
Страница 485: ......
Страница 486: ...Public Information ...