CHAPTER 10: MAINTENANCE
COPY SETTINGS TO OTHER DEVICE
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
10-7
10
10.5 Copy settings to other device
Settings from one M60 device can be copied to another M60 device for rapid deployment. The order codes must match.
See the Settings File section at the beginning of the Interfaces chapter for a list of settings not deployed, such as IP
address.
To apply settings to another device:
1.
Right-click the device in the Online window and select the
Add Device to Offline Window
option. A window opens.
2.
Check the file path and name the file, then click the
Receive
button. An example is to save the files in
D:\Users\Public\Public Documents\GE Power Management\URPC\Data\ and to name the source device
M60_Deployment. At the prompt, confirm the action. The settings are saved in .cid, .icd, and .urs files, and the entry
displays in the Offline window area.
3.
Right-click the device in the Offline window area and select the
Duplicate Device
option. The device is copied with a
prefix of "Copy of." Multiple duplicates results in files being named "Copy of Copy of" for example, which can be
avoided by deleting the folder copies from the path shown on mouse-over.
4.
Right-click the copied device and rename it.
5.
Right-click the copied device and select the
Edit Device Properties
option. Make the changes for the new device.
6.
Send the file to new device by dragging and dropping it into the Online Window area. Or right-click and select the
Write Settings to Device
option.
7.
Update the remaining settings, such as IP address.
10.6 Compare settings
Settings are comparable against default values and between two UR devices.
Some of the IEC 61850 settings use floating point data, which guarantees accurate representation of real numbers up to
seven digits. Numbers with more than seven digits are approximated within a certain precision. This can result in
differences between what is entered and what is saved, and for example results in differences shown on a settings
comparison report.
When comparing two settings files with the graphical front panel, all graphical front panel features are compared except
for the single-line diagrams.
10.6.1 Compare against defaults
To compare settings against default values:
1.
Right-click the device in the Offline Window area and select
Compare Settings With Defaults
. The file generates and
the number of differences displays.
2.
To save the report, click
File > Save As
, select the TXT, PDF, or CSV format from the drop-down list, and enter a name
for the file.
In the figure, the first entry (red) is from the device, while the second (green) is the default value.
Figure 10-7: Device settings compared with default values
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...