CHAPTER 6: ACTUAL VALUES
STATUS
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
6-11
6
CHANNEL 1 STATUS
— This represents the receiver status of each channel. If the value is “OK,” teleprotection is enabled and
data is being received from the remote terminal; If the value is “FAIL,” teleprotection enabled and data is not being received
from the remote terminal. If “n/a,” teleprotection is disabled.
CHANNEL 1 LOST PACKETS
— Data is transmitted to the remote terminals in data packets at a rate of two packets per cycle.
The number of lost packets represents data packets lost in transmission; this count can be reset to 0 through the
COMMANDS
CLEAR RECORDS
menu.
VALIDITY OF CHANNEL CONFIGURATION
— This value displays the current state of the communications channel identification
check, and hence validity. If a remote relay ID does not match the programmed ID at the local relay, the “FAIL” message
displays. The “N/A” value appears if the local relay ID is set to a default value of “0,” the channel is failed, or if the
teleprotection inputs/outputs are not enabled.
6.3.20 Remaining connection status
ACTUAL VALUES
STATUS
COMM STATUS REMAINING CONNECT
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
MMS TCP
— The number of IEC 61850 connections remaining.
6.3.21 Parallel Redundancy Protocol (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES
STATUS
PRP STATUS
COMM STATUS
REMAINING CONNECT
MMS TCP(max 5)
5
Range: 0 to 5
MODBUS TCP (max 4)
4
Range: 0 to 4
DNP TCP(max 2)
2
Range: 0 to 2
IEC-104 TCP(max 2)
2
Range: 0 to 2
SFTP (max 4)
4
Range: 0 to 4
PRP STATUS
Total Rx Port A:
0
Range: 0 to 4G, blank if PRP disabled
Total Rx Port B:
0
Range: 0 to 4G, blank if PRP disabled
Mismatches Port A:
0
Range: 0 to 4G, blank if PRP disabled
Mismatches Port B:
0
Range: 0 to 4G, blank if PRP disabled
Total Errors:
0
Range: 0 to 4G, blank if PRP disabled
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...