CHAPTER 5: SETTINGS
PRODUCT SETUP
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
5-51
5
The
PROTOCOL
menu allows selection of one of the following protocols: DNP 3.0, IEC60870-104, or IEC60870-103.
SCADA PROTOCOL
— This setting selects the SCADA protocol on which the unit communicates, among DNP3.0, IEC 60870-
104, and IEC 60870-103, with DNP being the default. Options depend on order code. For any change to take effect, restart
the unit.
MMS CONNECTION TIMEOUT
— This setting specifies a time delay for the detection of network TCP connection lost. If there is
no data traffic on the TCP connection for greater than the time specified by this setting, the connection is aborted. This
frees up the connection to be re-used by a client. For any change to take effect, restart the unit.
The table shows which of DNP 3.0, IEC 60870-5-104, IEC 60870-5-103, and IEC 61850 protocols are operational on the
RS232, RS485, and Ethernet ports. It shows all possible combinations of the
PROTOCOL
and
DNP CHANNEL 1(2) PORT
settings.
Table 5-9: Port and protocol combinations
5.3.5.10 DNP protocol
SETTINGS
PRODUCT SETUP
COMMUNICATIONS
DNP PROTOCOL
MMS CONNECTION
TIMEOUT: 120 s
Range: 10 to 7200 in steps of 10
PROTOCOL
setting
DNP CHANNEL 1(2) PORT
settings
RS232
RS485
Ethernet
DNP
Channel 1: Eth TCP
Channel 2: Eth TCP
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: none
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: none
Channel 2: Eth TCP
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: none
Modbus
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS485
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: Eth TCP
Channel 2: RS232
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS485
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: Eth UDP
Channel 2: RS232
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: Eth TCP
Modbus
DNP
DNP, Modbus, IEC 61850
Channel 1: RS232
Channel 2: Eth TCP
DNP
Modbus
DNP, Modbus, IEC 61850
Channel 1: RS485
Channel 2: RS232
DNP
DNP
Modbus, IEC 61850
Channel 1: RS232
Channel 2: RS485
DNP
DNP
Modbus, IEC 61850
Channel 1: RS485
Channel 2: none
Modbus
DNP
Modbus, IEC 61850
IEC 104
Modbus
Modbus
IEC 104, Modbus, IEC 61850
IEC 103
Modbus
IEC 103
Modbus, IEC 61850
DNP PROTOCOL
DNP CHANNELS
See below
DNP ADDRESS:
1
Range: 0 to 65535 in steps of 1
DNP NETWORK
CLIENT ADDRESSES
See below
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...