2-2
M60 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
PRODUCT DESCRIPTION
CHAPTER 2: PRODUCT DESCRIPTION
2
port supports IEC 61850, Modbus/TCP, TFTP, and PTP (according to IEEE Std. 1588-2008 or IEC 61588), and it allows access
to the relay via any standard web browser (M60 web pages). The IEC 60870-5-104 protocol is supported on the Ethernet
port. The Ethernet port also supports the Parallel Redundancy Protocol (PRP) of IEC 62439-3 (clause 4, 2012) when
purchased as an option.
Secure Routable GOOSE (R-GOOSE) is supported with software options.
The EnerVista UR Setup software suite contains an automatic configurator for motor starting settings. The configurator
automatically populates settings and operands for input relays, output relays, trip bus, AC inputs, and signal sources based
on user requirements and the relay features.
Settings and actual values can be accessed from the front panel or EnerVista software.
The M60 uses flash memory technology that allows field upgrading as new features are added. Firmware and software are
upgradable.
The following single-line diagram illustrates the relay functionality using American National Standards Institute (ANSI)
device numbers.
Table 2-1: ANSI device numbers and functions supported
Device number Function
Device number Function
27P
Phase Undervoltage
51N
Neutral Time Overcurrent
27X
Auxiliary Undervoltage
51P
Phase Time Overcurrent
32
Sensitive Directional Power
59N
Neutral Overvoltage
37
Undercurrent
59P
Phase Overvoltage
37P
Underpower
59X
Auxiliary Overvoltage
46
Current Unbalance
59_2
Negative Sequence Overvoltage
47
Phase Sequence Voltage
66
Starts Per Hour, Time Between Starts
49
Thermal Model
67N
Neutral Directional Overcurrent
50BF
Breaker Failure
67P
Phase Directional Overcurrent
50G
Ground Instantaneous Overcurrent
81O
Overfrequency
50N
Neutral Instantaneous Overcurrent
81U
Underfrequency
50P
Phase Instantaneous Overcurrent
87S
Stator Differential
51G
Ground Time Overcurrent
---
Mechanical Jam
Содержание M60
Страница 9: ...TABLE OF CONTENTS M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ix INDEX ...
Страница 10: ...x M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 208: ...4 88 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 494: ...5 286 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL CONTROL ELEMENTS CHAPTER 5 SETTINGS 5 Figure 5 158 Time out mode ...
Страница 552: ...5 344 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 596: ...7 14 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 602: ...9 4 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SATURATION DETECTOR CHAPTER 9 THEORY OF OPERATION 9 ...
Страница 652: ...C 6 M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 660: ...iv M60 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...