CHAPTER 1: INTRODUCTION
FEATURES
LM10 MOTOR PROTECTION SYSTEM – INSTRUCTION MANUAL
1–5
•
Baud rate
: This two-position DIP switch is used to select the DeviceNet baud rate. The
valid rates are 125K, 250K and 500K bits per second. The DIP switch is defaulted to
125K baud rate when shipped.
Changes to switch settings will not take effect until the next power cycle.
•
Trip Class (TC)
: NEMA overload trip class is selected using a rotary DIP switch. Valid
settings are Class 10, 15, 20, or 30. To set the trip class, align the screwdriver slot with
the desired value. Do not use the triangle marker on the DIP switch. A screwdriver with
a nominal blade width of 0.094 to 0.175 inches should be used. Smaller blades could
allow the switch to be set in an invalid position.
Changes to switch settings will not take effect until power is cycled.
FIGURE 1–2: LM10 Features
Baud Rate
DIP Switch Position
125 kbps
down - down
250 kbps
up - down
500 kbps
up - up
849713A3.CDR
Display
Liquid crystal display: four lines
of 16 characters per line.
Status
The status sub-menu can display
current, motor status, Run 1 and
Run 2 data, faults, MAC ID, baud
rate, and overload class.
Reset
The relay can be reset from the
PDU, pushbutton, or the LAN.
Mounting Flexibility
The relay can be attached to the
PDU without hardware to
facilitate door mounting.
LEDS
One green LED power indicator
and a flashing red trip LED to
indicate over/undercurrent,
current unbalance, ground
fault, under/overvoltage, and
trip command.
CONFIG
The relay parameters are
programmed via the CONFIG
button. The CONFIG sub-menu is
similar to the status menu, and
allows the user to change relay
parameters: CT ratio, PT ratio,
fault settings, and time delays.
History
Displays the last ten (10) trip
records. The conditions at the
time of fault are displayed and
can be scrolled through using
the UP/DOWN arrow keys.
Содержание LM10
Страница 6: ...1 IV LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 18: ...1 12 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 1 INTRODUCTION ...
Страница 50: ...4 44 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL MOTOR START STOP LOGIC CHAPTER 4 FUNCTIONALITY ...
Страница 70: ...5 64 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL SERIAL PORT CHAPTER 5 COMMUNICATIONS ...
Страница 74: ...6 68 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL WARRANTY CHAPTER 6 MISCELLANEOUS ...
Страница 102: ...A 28 LM10 MOTOR PROTECTION SYSTEM INSTRUCTION MANUAL LM10 AND ALLEN BRADLEY SLC500 VIA DEVICENET CHAPTERA ...