2-52
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
2.6.13 Type tests
L90 TYPE TESTS
1 Not tested by third party.
2.6.14 Production tests
THERMAL
Products go through an environmental test based upon an Accepted Quality Level (AQL) sampling process.
Test
Reference standard
Test level
Dielectric voltage withstand
EN 60255-5
1
2.2 kV
Impulse voltage withstand
EN 60255-5
1
5 kV
Damped oscillatory
IEC 61000-4-18 / IEC 60255-22-1
2.5 kV CM, 1 kV DM
Electrostatic discharge
EN 61000-4-2 / IEC 60255-22-2
Level 3
RF immunity
EN 61000-4-3 / IEC 60255-22-3
Level 3
Fast transient disturbance
EN 61000-4-4 / IEC 60255-22-4
Class A and B
Surge immunity
EN 61000-4-5 / IEC 60255-22-5
Level 3 and 4
Conducted RF immunity
EN 61000-4-6 / IEC 60255-22-6
Level 3
Power frequency immunity
EN 61000-4-7
1
/ IEC 60255-22-7
Class A and B
Voltage interruption and ripple DC
IEC 60255-11
12% ripple, 200 ms interrupts
Radiated and conducted emissions
CISPR11 / CISPR22 / IEC 60255-25
Class A
Sinusoidal vibration
IEC 60255-21-1
Class 1
Shock and bump
IEC 60255-21-2
Class 1
Seismic
IEC 60255-21-3
Class 1
Power magnetic immunity
IEC 61000-4-8
Level 5
Pulse magnetic immunity
IEC 61000-4-9
Level 4
Damped magnetic immunity
IEC 61000-4-10
Level 4
Voltage dip and interruption
IEC 61000-4-11
0, 40, 70, 80% dips; 250 / 300 cycle interrupts
Damped oscillatory
IEC 61000-4-12
1
2.5 kV CM, 1 kV DM
Conducted RF immunity, 0 to 150 kHz
IEC 61000-4-16
Level 4
Voltage ripple
IEC 61000-4-17
15% ripple
Ingress protection
IEC 60529
1
IP20 front, IP10 back
Cold
IEC 60068-2-1
–40°C for 16 hours
Hot
IEC 60068-2-2
85°C for 16 hours
Humidity
IEC 60068-2-30
6 days, variant 1
Damped oscillatory
IEEE/ANSI C37.90.1
2.5 kV, 1 MHz
RF immunity
IEEE/ANSI C37.90.2
20 V/m, 80 MHz to 1 GHz
Safety
UL 508
e83849 NKCR
Safety
UL C22.2-14
e83849 NKCR7
Safety
UL 1053
e83849 NKCR
Safety
IEC 60255-27
Insulation: class 1, Pollution degree: 2, Over
voltage cat II
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...