L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
CONTROL ELEMENTS
CHAPTER 5: SETTINGS
5
relays, and the breaker mechanism. For maximum measurement accuracy, measure the interval between change-of-state
of the operand (from 0 to 1) and contact separation for the specific installation. Integration of the measured current
continues for 100 ms, which is expected to include the total arcing period.
The feature is programmed to perform fault duration calculations. Fault duration is defined as a time between operation of
the disturbance detector occurring before initiation of this feature, and reset of an internal low-set overcurrent function.
Correction is implemented to account for a non-zero reset time of the overcurrent function.
Breaker arcing currents and fault duration values are available under the
ACTUAL VALUES
RECORDS
MAINTENANCE
BREAKER 1(4)
menus.
BKR 1 ARC AMP INT-A(C)
— Select the same output operands that are configured to operate the output relays used to trip the
breaker. In three-pole tripping applications, configure the same operand to initiate arcing current calculations for poles A,
B, and C of the breaker. In single-pole tripping applications, configure per-pole tripping operands to initiate the calculations
for the poles that are actually tripped.
BKR 1 ARC AMP DELAY
— This setting is used to program the delay interval between the time the tripping sequence is
initiated and the time the breaker contacts are expected to part, starting the integration of the measured current.
BKR 1 ARC AMP LIMIT
— Selects the threshold value above which the output operand is set.
BKR 1 CLR ARC AMPS
— Selects a FLexLogic Operand to clear the accumulated I
2
t values (kA
2
-cycle), reset fault duration
items (breaker operating time), clear ARCING AMPS (kA
2
-cycle) and AMP MAX (kA) values of the last event.
BKR 1 INTERUPTION RATING
— This setting specifies the maximum symmetrical interruption rating of the circuit breaker.
Figure 5-202: Arcing current measurement
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...