2-42
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
SPECIFICATIONS
CHAPTER 2: PRODUCT DESCRIPTION
2
DIGITAL ELEMENTS
Number of elements:
48
Operating signal:
any FlexLogic operand
Pickup delay:
0.000 to 999999.999 s in steps of 0.001
Dropout delay:
0.000 to 999999.999 s in steps of 0.001
Timing accuracy:
±3% or ±4 ms, whichever is greater
2.6.3 Monitoring
OSCILLOGRAPHY
Maximum records:
64
Sampling rate:
64 samples per power cycle
Triggers:
any element pickup, dropout, or operate; contact input change of state; contact output change
of state; FlexLogic equation
Data:
AC input channels; element state; contact input state; contact output state
Data storage:
in non-volatile memory
EVENT RECORDER
Capacity:
1024 events
Time-tag:
to 1 microsecond
Triggers:
any element pickup, dropout, or operate; contact input change of state; contact output change
of state; self-test events
Data storage:
in non-volatile memory
DATA LOGGER
Number of channels:
1 to 16
Parameters:
any available analog actual value
Sampling rate:
15 to 3600000 ms in steps of 1
Trigger:
any FlexLogic operand
Mode:
continuous or triggered
Storage capacity:
(NN is dependent on memory)
1-second rate:
01 channel for NN days
16 channels for NN days
↓
60-minute rate:
01 channel for NN days
16 channels for NN days
FAULT LOCATOR
Number of independent fault locators: 1 per CT bank (to a maximum of 4)
Method:
multi-ended or single-ended during channel failure
Voltage source:
wye-connected VTs, delta-connected VTs and neutral voltage, delta-connected VTs and zero-
sequence current (approximation)
Maximum accuracy if:
fault resistance is zero or fault currents from all line terminals are in phase
Relay accuracy:
±1.5% (V > 10 V, I > 0.1 pu)
Worst-case accuracy:
VT
%error
+
user data
CT
%error
+
user data
Z
Line%error
+
user data
METHOD
%error
+
0.5% (multi-ended method)
See Theory of Operation chapter (single-ended method)
RELAY ACCURACY
%error
+
1.5%
PHASOR MEASUREMENT UNIT
Output format:
per IEEE C37.118 or IEC 61850-90-5 standard
Number of channels:
14 synchrophasors, 8 analogs, 16 digitals
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...