CHAPTER 2: PRODUCT DESCRIPTION
SPECIFICATIONS
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
2-33
2
Pickup:
0.050 to 30.000 pu in steps of 0.001
Dropout:
97 to 98%
Memory duration:
5 to 25 cycles in steps of 1
Voltage supervision pickup (series compensation applications):
0 to 5.000 pu in steps of 0.001
GROUND DISTANCE OPERATING TIME CURVES
The operating times are response times of a microprocessor part of the relay. See output contacts specifications for estimation of the
total response time for a particular application. The operating times are average times including variables such as fault inception angle
or type of a voltage source (magnetic VTs and CVTs). The figure shows zone 1 ground distance time curves for a 60 Hz system at nominal
system frequency.
LINE PICKUP
Phase instantaneous overcurrent:
0.020 to 30.000 pu
Undervoltage pickup:
0.004 to 3.000 pu
Overvoltage delay:
0.000 to 65.535 s
LINE CURRENT DIFFERENTIAL (87L)
Application:
2 or 3 terminal line, series compensated line, tapped line, with charging current compensation
Characteristic:
Dual slope percent differential
Pickup current level:
0.20 to 4.00 pu in steps of 0.01
CT Tap (CT mismatch factor):
0.20 to 5.00 in steps of 0.01
Slope # 1:
1 to 50%
Slope # 2:
1 to 70%
Level accuracy:
±3% of reading of the maximum circuit current
Breakpoint between slopes:
0.0 to 20.0 pu in steps of 0.1
DTT:
Direct Transfer Trip (1 and 3 pole) to remote L90
Operating Time:
1.0 to 1.5 power cycles duration
Asymmetrical channel delay compensation using GPS:
asymmetry up to 10 ms
In-zone transformer group compensation: 0 to 330° in steps of 30°
Inrush inhibit level:
1.0 to 40.0%f
0
in steps of 0.1
Inrush inhibit mode:
per-phase, 2-out-of-3, average
Zero-sequence current differential (87LG):
87LG pickup level:
0.05 to 1.00 pu in steps of 0.01
87LG slope:
1 to 50%
87LG pickup delay:
0.00 to 5.00 s in steps of 0.01
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...