CHAPTER 5: SETTINGS
FLEXLOGIC
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
5-187
5
R-SV CB1 SVENA DFLT
— This setting sets the default state of the stream (On or Off) on power-up or restart.
R-SV CB1 CONFREV
— The relay increments the Configuration revision every time the configuration is changed. This setting
allows the user to reset the configuration back to 1 or a value from 1 to 4294967295.
R-SV CB1 PRIORITY
— A value from 0 through 7. The default value is 4.
R-SV CB1 DSCP CLASS
— The value represents the IPv4 Differentiated Services (formerly called TypeOfService) value. The
default value is set for Expedited Forwarding (101110B (46 or 2EH). This value provides priority routing, when supported in
the routers.
R-SV CB1 VLAN ID
— A range of values limited from 0 to 4095.
R-SV CB1 APPID
— This setting allows the selection of a specific application ID for each sending device.
R-SV CB1 DEST IP
— This is the destination multicast IP address that is entered in Standard IPV4 address format. The valid
range for IPv4 is from 224.0.0.0 to 239.255.255.255. The UR does not test the address entered.
R-SV CB1 SECURITY
— This setting selects the level of security and authentication used, as outlined in the following table,
and is in the form of an enumeration as per standard. The range is 0 to 2.
Table 5-22: Security
5.6 FlexLogic
5.6.1 FlexLogic operands
For flexibility, the arrangement of internal digital logic combines fixed and user-programmed parameters. Logic upon
which individual features are designed is fixed, and all other logic, from contact input signals through elements or
combinations of elements to contact outputs, is variable. The user has complete control of all variable logic through
FlexLogic. In general, the system receives analog and digital inputs that it uses to produce analog and digital outputs. The
figure shows major subsystems of a generic UR-series relay involved in this process.
Shaded settings in the table are not supported in firmware 7.0.
Enumeration
Authentication
Encryption
0
No
No
1
Yes
No
2
Yes
Yes
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...