4-60
L90 LINE CURRENT DIFFERENTIAL SYSTEM – INSTRUCTION MANUAL
FRONT PANEL INTERFACE
CHAPTER 4: INTERFACES
4
4.2.9.1 Control mode selection and monitoring
Installations can require that a breaker be operated in the three-pole only mode (3-pole), or in the one and three-pole (1-
pole) mode, selected by setting. If the mode is selected as three-pole, a single input tracks the breaker open or closed
position. If the mode is selected as one-pole, all three breaker pole states must be input to the relay. These inputs must be
in agreement to indicate the position of the breaker.
For the following discussion it is assumed that the
SETTINGS
SYSTEM SETUP
BREAKERS
BREAKER 1(2)
BREAKER
1(2) PUSH BUTTON CONTROL
setting is “Enabled” for each breaker.
4.2.9.2 Front panel (user key) control
After the 30 minute interval during which command functions are permitted after a correct command password, the user
cannot open or close a breaker via the keypad. The following discussions begin from the not-permitted state.
4.2.9.3 Control of two breakers
For the following setup example, the
(Name)
field represents the user-programmed variable name.
For this example, the relay is connected and programmed for both breaker 1 and breaker 2. The
USER 1
key performs the
selection of which breaker is to be operated by the
USER 2
and
USER 3
keys. The
USER 2
key manually closes the breaker, and
the
USER 3
key manually opens the breaker.
4.2.9.4 Control of one breaker
For this application, the relay is connected and programmed for breaker 1 only. Operation for this application is identical to
that described in the previous section for two breakers.
4.2.10 Change passwords
The information in this section refers to password security. For information on how to set the password for the first time or
change CyberSentry passwords, see the previous chapter or the Settings > Product Setup > Security > CyberSentry section
in the next chapter.
ENTER COMMAND
PASSWORD
This message appears when the
USER 1
,
USER 2
, or
USER
3 key is pressed and a
COMMAND
PASSWORD
is required, that is, if
COMMAND PASSWORD
is enabled and no commands have been
issued within the last 30 minutes.
Press USER 1
To Select Breaker
This message appears if the correct password is entered or if none is required. This message
displays for 30 seconds or until the
USER 1
key is pressed again.
BKR1-(Name) SELECTED
USER 2=CLS/USER 3=OP
This message displays after the
USER 1
key is pressed for the second time. Three possible actions
can be performed from this state within 30 seconds as per the following items (1), (2) and (3).
(1)
USER 2 OFF/ON
To Close BKR1-(Name)
If the
USER 2
key is pressed, this message appears for 20 seconds. If the
USER 2
key is pressed
again within that time, a signal is created that can be programmed to operate an output relay to
close breaker 1.
(2)
USER 3 OFF/ON
To Open BKR1-(Name)
If the
USER 3
key is pressed, this message appears for 20 seconds. If the
USER 3
key is pressed
again within that time, a signal is created that can be programmed to operate an output relay to
open breaker 1.
(3)
BKR2-(Name) SELECTED
USER 2=CLS/USER 3=OP
If the
USER 1
key is pressed at this step, this message appears showing that a different breaker is
selected. Three possible actions can be performed from this state as per (1), (2) and (3). Repeatedly
pressing the
USER 1
key alternates between available breakers. Pressing keys other than
USER 1
,
2
,
or
3
at any time cancels the breaker control function.
Содержание L90
Страница 14: ...1 4 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 68: ...2 54 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL SPECIFICATIONS CHAPTER 2 PRODUCT DESCRIPTION 2 ...
Страница 136: ...3 68 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 224: ...4 88 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FLEXLOGIC DESIGN USING ENGINEER CHAPTER 4 INTERFACES 4 ...
Страница 692: ...6 36 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL PRODUCT INFORMATION CHAPTER 6 ACTUAL VALUES 6 ...
Страница 708: ...7 16 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 742: ...9 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 9 COMMISSIONING 9 ...
Страница 804: ...10 62 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL FAULT LOCATOR CHAPTER 10 THEORY OF OPERATION 10 ...
Страница 872: ...C 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 878: ...D 6 L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL REVISION HISTORY APPENDIX D MISCELLANEOUS D ...
Страница 882: ...iv L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...
Страница 900: ...xviii L90 LINE CURRENT DIFFERENTIAL SYSTEM INSTRUCTION MANUAL INDEX ...