CHAPTER 6: ACTUAL VALUES
STATUS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
6-11
6
These values specify the remaining number of TCP connections still available for each protocol. The display depends on the
options applicable to your device. Each time a connection is used, the remaining number of connections decrements.
When released, the remaining number of connections increments. If no connection is made over the specific protocol, the
number equals the maximum number available for the specific protocol.
For example, the maximum number of Modbus TCP connections is 4. Once an EnerVista session is opened on a computer
connected to the UR over Ethernet, the Modbus TCP status shows 3. If the EnerVista application is closed, the Modbus TCP
status shows 4.
For the graphical front panel, the remaining connections refer to TCP connections only.
MMS TCP
— The number of IEC 61850 connections remaining.
6.3.20 Parallel Redundancy Protocol (PRP)
The Parallel Redundancy Protocol (PRP) defines a redundancy protocol for high availability in substation automation
networks.
ACTUAL VALUES
STATUS
PRP STATUS
Total Received Port A
is a counter for total messages received (either from DANPs or from SANs) on Port A.
Total Received Port B
is a counter for total messages received (either from DANPs or from SANs) on Port B.
Total Errors
is a counter for total messages received with an error (bad port code, frame length too short).
Mismatches Port A
is a counter for total messages received with an error on Port A (PRP frame, but port received through
and LAN ID in the frame do not match).
Mismatches Port B
is a counter for total messages received with an error on Port B (PRP frame, but port received through
and LAN ID in the frame do not match).
6.3.21 TxGOOSE status
ACTUAL VALUES
STATUS
TxGOOSE STATUS
PRP STATUS
Total Rx Port A:
0
Range: 0 to 4G, blank if PRP disabled
Total Rx Port B:
0
Range: 0 to 4G, blank if PRP disabled
Mismatches Port A:
0
Range: 0 to 4G, blank if PRP disabled
Mismatches Port B:
0
Range: 0 to 4G, blank if PRP disabled
Total Errors:
0
Range: 0 to 4G, blank if PRP disabled
The L60 is provided with optional PRP capability. This feature is specified as a software option at the time of
ordering. See the Order Codes section in chapter 2 for details.
TxGOOSE STATUS
R-TxGOOSE 1
ARP: Off
Range: On, Off
R-TxGOOSE 16
ARP: Off
Range: On, Off
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...