CHAPTER 5: SETTINGS
CONTROL ELEMENTS
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
5-355
5
Figure 5-199: Single-pole autoreclose logic (Sheet 1 of 3)
In runtime, AR mode can be changed through the mode control logic as shown in the following diagram. Initially, the
autorecloser runs in the mode as per
AR MODE
setting. Then the relay checks the AR activation inputs in each protection
pass. The AR mode is switched to the new mode when
•
Only one of four activation inputs is high, and
•
AP RIP
operand is low, and
•
The mode to be activated is different from the current AR mode
The logic allows activation of one mode at a time. Simultaneous multiple activations are ignored and mode switching does
not happen. However, a FlexLogic operand,
AR MODE SWITCH FAIL
, is asserted if either simultaneous multiple activations are
initiated, or a single activation is initiated but recloser is already in progress.
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...