5-276
L60 LINE PHASE COMPARISON SYSTEM – INSTRUCTION MANUAL
GROUPED ELEMENTS
CHAPTER 5: SETTINGS
5
Figure 5-153: Negative-sequence directional OC1 logic
5.6.13 Breaker failure (ANSI 50BF)
SETTINGS
GROUPED ELEMENTS
SETTING GROUP 1(6)
BREAKER FAILURE
BREAKER FAILURE 1(2)
BREAKER FAILURE 1
BF1 FUNCTION:
Disabled
Range: Disabled, Enabled
BF1 MODE:
3-Pole
Range: 3-Pole, 1-Pole
BF1 SOURCE:
SRC 1
Range: SRC 1, SRC 2, SRC 3, SRC 4
BF1 USE AMP SUPV:
Yes
Range: Yes, No
BF1 USE SEAL-IN:
Yes
Range: Yes, No
BF1 3-POLE INITIATE:
Off
Range: FlexLogic operand
BF1 BLOCK:
Off
Range: FlexLogic operand
BF1 RETRIP PICKUP
DELAY: 0.033 s
Range: 0.000 to 65.535 s in steps of 0.001
BF1 PH AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 N AMP SUPV
PICKUP: 1.050 pu
Range: 0.020 to 30.000 pu in steps of 0.001
BF1 USE TIMER 1:
Yes
Range: Yes, No
Содержание L60
Страница 10: ...x L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TABLE OF CONTENTS ...
Страница 14: ...1 4 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FOR FURTHER ASSISTANCE CHAPTER 1 INTRODUCTION 1 ...
Страница 122: ...3 72 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL CONNECT TO D400 GATEWAY CHAPTER 3 INSTALLATION 3 ...
Страница 590: ...5 382 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TESTING CHAPTER 5 SETTINGS 5 ...
Страница 632: ...7 12 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL TARGETS MENU CHAPTER 7 COMMANDS AND TARGETS 7 ...
Страница 736: ...A 14 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL FLEXANALOG ITEMS APPENDIX A FLEXANALOG OPERANDS A ...
Страница 744: ...C 6 L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL COMMAND LINE INTERFACE APPENDIX C COMMAND LINE INTERFACE C ...
Страница 752: ...iv L60 LINE PHASE COMPARISON SYSTEM INSTRUCTION MANUAL ABBREVIATIONS ...