GE Multilin
L60 Line Phase Comparison Relay
B-17
APPENDIX B
B.4 MEMORY MAPPING
B
3519
RTD Input 42 Value
-32768 to 32767
°C
1
F002
0
351A
RTD Input 43 Value
-32768 to 32767
°C
1
F002
0
351B
RTD Input 44 Value
-32768 to 32767
°C
1
F002
0
351C
RTD Input 45 Value
-32768 to 32767
°C
1
F002
0
351D
RTD Input 46 Value
-32768 to 32767
°C
1
F002
0
351E
RTD Input 47 Value
-32768 to 32767
°C
1
F002
0
351F
RTD Input 48 Value
-32768 to 32767
°C
1
F002
0
Expanded Direct Input/Output Status (Read Only)
3560
Direct Device States, one per register (8 items)
0 to 1
---
1
F155
0 (Offline)
3570
Direct Input States, one per register (96 items)
0 to 1
---
1
F108
0 (Off)
Passwords (Read/Write Command)
4000
Command Password Setting
0 to 4294967295
---
1
F003
0
Passwords (Read/Write Setting)
4002
Setting Password Setting
0 to 4294967295
---
1
F003
0
Passwords (Read/Write)
4008
Command Password Entry
0 to 4294967295
---
1
F003
0
400A
Setting Password Entry
0 to 4294967295
---
1
F003
0
Passwords (Read Only)
4010
Command Password Status
0 to 1
---
1
F102
0 (Disabled)
4011
Setting Password Status
0 to 1
---
1
F102
0 (Disabled)
User Display Invoke (Read/Write Setting)
4040
Invoke and Scroll Through User Display Menu Operand
0 to 65535
---
1
F300
0
LED Test (Read/Write Setting)
4048
LED Test Function
0 to 1
---
1
F102
0 (Disabled)
4049
LED Test Control
0 to 65535
---
1
F300
0
Preferences (Read/Write Setting)
404F
Language
0 to 3
---
1
F531
0 (English)
4050
Flash Message Time
0.5 to 10
s
0.1
F001
10
4051
Default Message Timeout
10 to 900
s
1
F001
300
4052
Default Message Intensity
0 to 3
---
1
F101
0 (25%)
4053
Screen Saver Feature
0 to 1
---
1
F102
0 (Disabled)
4054
Screen Saver Wait Time
1 to 65535
min
1
F001
30
4055
Current Cutoff Level
0.002 to 0.02
pu
0.001
F001
20
4056
Voltage Cutoff Level
0.1 to 1
V
0.1
F001
10
Communications (Read/Write Setting)
407E
COM1 minimum response time
0 to 1000
ms
10
F001
0
407F
COM2 minimum response time
0 to 1000
ms
10
F001
0
4080
Modbus Slave Address
1 to 254
---
1
F001
254
4083
RS485 Com1 Baud Rate
0 to 11
---
1
F112
8 (115200)
4084
RS485 Com1 Parity
0 to 2
---
1
F113
0 (None)
4085
RS485 Com2 Baud Rate
0 to 11
---
1
F112
8 (115200)
4086
RS485 Com2 Parity
0 to 2
---
1
F113
0 (None)
4087
IP Address
0 to 4294967295
---
1
F003
56554706
4089
IP Subnet Mask
0 to 4294967295
---
1
F003
4294966272
408B
Gateway IP Address
0 to 4294967295
---
1
F003
56554497
408D
Network Address NSAP
---
---
---
F074
0
409A
DNP Channel 1 Port
0 to 4
---
1
F177
0 (None)
409B
DNP Channel 2 Port
0 to 4
---
1
F177
0 (None)
409C
DNP Address
0 to 65519
---
1
F001
1
409D
Reserved
0 to 1
---
1
F001
0
409E
DNP Client Addresses (2 items)
0 to 4294967295
---
1
F003
0
40A3
TCP Port Number for the Modbus protocol
1 to 65535
---
1
F001
502
40A4
TCP/UDP Port Number for the DNP Protocol
1 to 65535
---
1
F001
20000
40A5
TCP Port Number for the HTTP (Web Server) Protocol
1 to 65535
---
1
F001
80
Table B–9: MODBUS MEMORY MAP (Sheet 10 of 47)
ADDR
REGISTER NAME
RANGE
UNITS
STEP
FORMAT
DEFAULT
Содержание L60
Страница 2: ......
Страница 4: ......
Страница 24: ...1 14 L60 Line Phase Comparison Relay GE Multilin 1 5 USING THE RELAY 1 GETTING STARTED 1...
Страница 42: ...2 18 L60 Line Phase Comparison Relay GE Multilin 2 2 SPECIFICATIONS 2 PRODUCT DESCRIPTION 2...
Страница 78: ...3 36 L60 Line Phase Comparison Relay GE Multilin 3 3 DIRECT INPUT OUTPUT COMMUNICATIONS 3 HARDWARE 3...
Страница 368: ...8 28 L60 Line Phase Comparison Relay GE Multilin 8 2 SINGLE POLE TRIPPING 8 THEORY OF OPERATION 8...
Страница 470: ...D 10 L60 Line Phase Comparison Relay GE Multilin D 1 PROTOCOL APPENDIXD D...
Страница 482: ...E 12 L60 Line Phase Comparison Relay GE Multilin E 2 DNP POINT LISTS APPENDIXE E...
Страница 498: ...x L60 Line Phase Comparison Relay GE Multilin INDEX Z ZERO SEQUENCE CORE BALANCE 3 9...